APC VS 50 Controls and Indicators, Mechanical, TWF0500H54B Rectifier, Magnum VS Controller

Models: VS 50 VS 100

1 65
Download 65 pages 5.73 Kb
Page 61
Image 61

9.3. Controls and Indicators

TWF0500H54B Rectifier

Input Healthy LED

AC power present.

 

 

Output Healthy LED

DC output voltage between 39.5 to 59.5 Vdc.

 

 

Current Limit LED

On when rectifier is in current limit.

 

 

Overvolts LED

On when rectifier is above 57 Vdc. (Must be powered down to

 

reset)

 

 

Magnum VS Controller

DC OK (Green)

On when voltage is between 50 and 57 Vdc.

 

 

Major (Red)

On when Major Relay is de-energized*

 

 

Minor (Yellow)

On when Minor Relay is energized

 

 

Out Relay 1 (Red)

On when Output Relay 1 is energized

 

 

(Flashing Green)

Watchdog LED

 

 

*Major relay is energized in normal operation. If all power fails, major relay will lose power and the contacts will change state, signifying an alarm.

9.4. Mechanical

TWF0500H54B Rectifier

Dimensions (Overall)

5 in (12.7 cm) high x 2.75 in (7 cm) wide x 10.5 in (26.7 cm)

 

deep

 

 

Dimensions (not including

5 in (12.7 cm) high x 2.5 in (6.3 cm) wide x 9.4 in (24 cm)

faceplate or connectors)

deep

 

 

Weight

4 lb (1.8 kg)

 

 

Color

Black front, Yellow zinc sides and back

 

 

Mounting

Hot swappable. Secured with 2.5 mm captive screws

 

 

Magnum VS 50 Power System

 

Magnum VS –48 Vdc User’s Manual

Page 56

Page 61
Image 61
APC VS 100 Controls and Indicators, Mechanical, TWF0500H54B Rectifier, Magnum VS Controller, Magnum VS 50 Power System