PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Rectifier Fault Alarm (RFA)

The status will be on if the rectifier output

Status Only

Status

has failed.

 

{Status Only}

 

 

[Power Modules/Rectifiers]

 

 

Rectifier RFA Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

or special rectifier alarm group n of N that

Output Relay 1-6,n of N

 

occurs when a rectifier output has failed.

 

Rectifier Standby Alarm

Defines the output relay that is that is

Ignore, Minor, Major

[Power Modules/Rectifiers]

energized or special rectifier alarm group

Output Relay 1-6, n of N

 

n of N that occurs when the controller is

 

 

holding a rectifier in the standby mode.

 

Rectifier Standby Alarm Status

The status will be “ON” if the controller is

This feature is supported

{Status Only}

holding the rectifier in the standby mode.

by the standard SNMP

[Power Modules/Rectifiers]

 

card monitor, but is not

 

 

supported by this dc

 

 

system.

Remote Configurable

This allows settings to be made using the

Enabled, Disabled

[System/DC Parameters]

SNMP interface card. Disabling this

 

 

feature allows changes to be made

 

 

through the local interface only. Status

 

 

and parameters are still displayed.

 

Store Configuration

This feature is supported by the standard

Enable, Disable

[Power Modules/Rectifiers]

SNMP card monitor, but is not supported

 

 

by this dc system.

 

System Current

The total system output current

Status Only

{Status Only}

(calculated as the sum of the individual

 

[System/DC Parameters]

rectifier output currents).

 

System Temperature

System temperature measured within the

Status Only

{Status Only}

controller.

 

[System/DC Parameters]

 

 

System Voltage

Voltage readout measured by the

Status Only

{Status Only}

controller at the output of the rectifiers.

 

[System/DC Parameters]

This voltage is based on calculations

 

 

performed by the controller based on the

 

 

Battery Float, Battery Temperature

 

 

Compensation and Battery Maximum

 

 

Recharge parameter settings.

 

Temperature Display Units

Enables selection of Fahrenheit or

Fahrenheit, Celsius

[System/Preferences]

Celsius temperature scale (Fahrenheit

 

 

“OFF” displays readings in °C).

 

Time

Network management card Internal

Current Time

[System/Date & Time]

system clock time (24-hour format).

 

 

Used as a time stamp in the web card

 

 

event log.

 

6.9. LVD Operation

In order to prevent damage to the battery due to deep discharge, the dc power system has a Low Voltage Disconnect (LVD). When the battery voltage reaches the threshold set by the LVD 1 Trip Voltage setting during discharge, the dc power system will activate the LVD contactor to disconnect the battery from the system. The LVD will remain open until ac power is restored to