PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

Settings in BOLD)

 

 

Battery Temperature

Battery temperature measured by the

Battery Temperature

[STATUS/BATTERY/

system controller at the optional battery

Status Only

PARAMETERS]

temperature sensor probe.

 

[状态 / 电池 /参数]

 

 

 

 

 

Date Setup

System date stored in the controller.

Current DATE

[SETUP/SYSTEM/TIME/DATE]

Used as a date stamp in the event log.

 

[设置 / 系统 / /]

 

 

 

 

 

Date Status

Displays the current controller date.

Date Status Only

[STATUS/SYSTEM/Time/Date]

 

 

[状态 / 系统 / /]

 

 

 

 

 

Equalize Automatically On/Off

Applies an overcharge to the battery to

ON, OFF

[SETUP/BATTERY/

equalize the specific gravity of a battery.

 

VOLTAGE/EQUALIZATION/

Auto equalization is initiated when the

 

METHOD/AUTO]

controller determines that the batteries

 

[设置 / 电池 /电压 /

have been discharged a set percentage

 

of their capacity or the batteries have

 

均充 / 模式 / 自动]

been on discharge for a set duration.

 

Use this screen to turn auto equalization

 

 

on.

 

Equalize Automatically on AC

Sets the time the ac input power has to

15 MINUTES – 360

Fail

be off before equalization occurs.

MINUTES, 15 MINUTES

[SETUP/BATTERY/

 

 

VOLTAGE/EQUALIZATION/

 

 

METHOD/AUTO/AC

 

 

FAIL/ON/OFF]

 

 

[设置 / 电池 /电压 /

 

 

均充 / 模式 / 自动

 

 

/自动]

 

 

 

 

 

Equalize Automatically on

Sets the percent of battery discharge

5% - 50%, 30 %

Battery Discharge

before equalization occurs. Percent

 

[SETUP/BATTERY/

Discharge = Discharged ampere-hours /

 

VOLTAGE/EQUALIZATION/

Battery Capacity ampere-hours

 

METHOD/AUTO/DISCHARGE]

 

 

[设置 / 电池 /电压 /

 

 

均充 / 模式 / 自动 /

 

 

交流故障]

 

 

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 31

Page 36
Image 36
APC VS 100, VS 50 user manual 设置 / 系统 / 时/日