Figure 6.8-1 Parameter Locations, Descriptions, and Settings

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Alarms Item 1

Display of up to 16 active alarms (a

No Alarms

{Status Only}

typical alarm screen is shown).

[System/Active Alarms]

No Alarms

Display of up to 16 active alarms (a

 

Alarms Item 16

typical alarm screen is shown).

 

[System/Active Alarms]

 

 

Battery Current

Battery current measured by the system

Status Only

{Status Only}

controller at the battery current shunt.

 

[System/DC Parameters]

 

 

Battery Discharge Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the battery discharge current exceeds

Output Relay 1-6

 

the programmed battery discharge

 

 

threshold.

 

Battery Discharge Threshold

An alarm is generated if the battery

0 A – 20A, 5 A

[Batteries/Parameters]

discharge current exceeds this value.

 

Battery Float Voltage

One of three parameters that control the

-56.5-47.0, -54.00 V

[Batteries/Parameters]

dc output voltage. Set the Float Voltage

 

 

at 25°C battery temperature per the

 

 

battery manufacturers recommendations.

 

Battery High Temperature

Defines the output relay that is energized

Ignore, Minor, Major

Alarm

if the battery temperature exceeds the

Output Relay 1-6

[Batteries/Parameters]

Battery High Temperature threshold.

 

Battery High Temperature

Battery Temperature is temperature

-100 °C – 200 °C, 40.0 °C

Threshold

measured at the battery probe. An alarm

 

[Batteries/Parameters]

is generated if the battery temperature

 

 

exceeds this value.

 

Battery High Voltage Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the dc output voltage rises above the

Output Relay 1-6

 

battery high voltage threshold.

 

Battery High Voltage Threshold

An alarm will be reported if temperature

-40.00 V – -60.00 V, -

[Batteries/Parameters]

is lower than the temperature entered.

58.00 V

 

An alarm is generated if the dc output

 

 

voltage rises above this value.

 

Battery Low Temperature

Defines the output relay that is energized

Ignore, Minor, Major

Alarm

if the Battery Temperature drops below

Output Relay 1-6

[Batteries/Parameters]

the battery Low Temperature threshold.

 

Battery Low Temperature

Battery Temperature is temperature

-100 °C – 200 °C, -20.0

Threshold

measured at the battery probe. An alarm

°C

[Batteries/Parameters]

is generated if the battery temperature

 

 

drops below this value.

 

Battery Low Voltage Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the dc output voltage drops below the

Output Relay 1-6

 

battery low voltage threshold.

 

Battery Low Voltage Threshold

An alarm is generated if the dc output

-40.00 V – -60.00 V,

[Batteries/Parameters]

voltage drops below this value.

-44.00 V