APC VS 100 user manual Specifications, AC Input, TWF0500H54B Rectifier, Magnum VS 50 Power System

Models: VS 50 VS 100

1 65
Download 65 pages 5.73 Kb
Page 58
Image 58
9 Specifications

9 Specifications

The overall system specifications can vary, depending upon the number of rectifier modules. Note that some specification items are provided on a “per rectifier” basis and must be combined or totaled for a given system configuration.

9.1. AC Input

TWF0500H54B Rectifier

Input Voltage Range

85

264 Vac

 

 

 

 

AC Frequency Range

47

63 Hz

 

 

Apparent Power Factor

99% Typical, 98% Minimum

 

 

Input Current (per Rectifier)

5.5 A @ 115Vac

 

3.7 A @ 230Vac

 

 

Turn on Time

2 Seconds

 

 

 

 

Magnum VS 50 Power System

 

 

 

 

 

 

 

Input Voltage Range

85

264 Vac

 

 

 

 

AC Frequency Range

47

63 Hz

 

 

Apparent Power Factor

99% Typical, 98% Minimum

 

 

 

Input Current

27.5

A @ 115 Vac

 

18.5 A @ 230 Vac

 

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 53

Page 58
Image 58
APC VS 100 user manual Specifications, AC Input, TWF0500H54B Rectifier, Magnum VS 50 Power System