Studer Innotec C2324 COMPACT, C1312 COMPACT Temperature sensor, Standard setting, Reset value

Page 19

STUDER INNOTEC

COMPACT

4.11 The Temperature sensor

Operating voltage of lead-acid batteries change depending on the temperature. To correct the operating voltages according to the actual temperatures, a temperature sensor can be connected to the COMPACT.

The compensation through the sensor is –3mV/°C/Cell.

Order Number: CT-35

Dimensions: H x B x T / 58 x 51.5 x 22mm

5 Programming:

5.1Standard setting

The COMPACT is delivered with the default setting following:

5.1.1Working mode

The working of the charger, the inverter and the transfer are describe in chapter 5.3/5.4/5.5.

5.1.2Battery voltage

Low voltage

11.6V / 23.2V / 46.4V

Float Charge

13.5V / 27.0V / 54.0V

End of Charge Voltage

14.4V / 28.8V / 57.6V

Equalization

15.3V / 30.6V / 61.2V

Absorption Time:

2 Hours

5.1.3Auxiliary contact

Active in case of defect or manual turn off with the LED 10/11/12/13

5.2Reset value

When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always programmed with these standard settings..

In order to get to these settings during operation you must press the three Push Buttons 20/21/22 simultaneously for a minimum of 2 seconds.

5.3Battery voltages and absorption time:

The voltage levels (low voltage, float charge, end of charge and equalization ) and the duration of the absorption charge can be changed.

The display of these voltages and the times in the program mode are in accordance with the diagram shown below:

5.3.1Table of voltage and timing threshold

 

Low voltage

Float Charge

Absorption

Equalization

Absorpt.

 

 

LED 13

 

 

LED 12

 

 

LED 11

 

 

LED 10

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED 10->13

LED

12V

 

24V

 

48V

12V

 

24V

 

48V

12V

 

24V

 

48V

12V

 

24V

 

48V

12/24/48V

14

12.0

 

24.0

 

48.0

13.7

 

27.4

 

54.8

16.2

 

32.4

 

64.8

16.2

 

32.4

 

64.8

4 h

15

11.8

 

23.6

 

47.2

13.6

 

27.2

 

54.4

15.6

 

31.2

 

62.4

15.9

 

31.8

 

63.6

3 h

16

11.6

 

23.2

 

46.4

13.5

 

27.0

 

54.0

15

 

30

 

60

15.6

 

31.2

 

62.4

2 h

17

11.4

 

22.8

 

45.6

13.4

 

26.8

 

53.6

14.4

 

28.8

 

57.6

15.3

 

30.6

 

61.2

1 h

18

11.2

 

22.4

 

44.8

13.3

 

26.6

 

53.2

14.2

 

28.4

 

56.8

15

 

30

 

60

0 – 1Min.

The heavy printed values show the standard settings.

User manual

COMPACT V2.0 E

19

Image 19
Contents Compact V2.0 E User and installer ManualIndex table Reset Value Battery Voltages and Absorption Time General Information Special Precautions Introduction Principe schematicDescription of main functions Parallel Connection Battery connectionsRemote control Solar charge regulator optionalConnection AssemblyPlace of assembly FixingProtection cover for the terminals connections Connecting Plan / Front sideSolar + Cabling/wiring Connection to Auxiliary Contact Connection to Remote controlConnection to Temperature Sensor Temp Connect the Solarmodules Solar +/- Only for solar optionDisplay and operating control elements OperatingPush buttons Light Emitting DiodesTurning Knobs Overload Battery ConditionInverter Charge detection system „StandbyEqualization charging Battery chargerInput current repartition Power sharing Cycle of chargeCharging current Transfer systemMultifunctional Contact Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Solar charge regulator optionMaximum Contact load -230Vac /16Amp-30Vdc/1A Remote ControlBattery voltages and absorption time Temperature sensorStandard setting Reset valueLED11 Program the auxiliary contactSet the voltage and timing threshold These four red LED show the function SetManual operating of Auxiliary Contact ExampleDiagram of the different mode MaintenanceVarious data Technical DataType Solar Charge Regulator-Floating