Thomas & Betts 20D, 15D owner manual Battery Cable Fusing, Recommended Fuse UL Listed Class T

Page 28

INSTALLATION

Battery Cable Fusing

A fuse is required by the NEC to protect the battery and cables. A UL Listed DC rated slow blow fuse must be installed in the positive

(+)battery cable, within 18 inches of the battery.

Recommended Fuse: UL Listed Class T

JLLN with a DC Rating. This fuse with fuse holder is available from your dealer or Heart Interface.

COMPRESSION / RING TERMINAL

 

NUT

 

LOCK WASHER

 

FLAT WASHER

INVERTER

BATTERY

CABLE

CABLE

 

 

FUSE

For Freedom 15 & 15D

 

 

200 Amp Fuse & Holder

PN# 84-4155-00 (C/R)*

200 Amp Fuse & Holder

PN# 84-4158-00 (R/R)**

200 Amp Fuse Only

PN# 84-4157-00

 

For Freedom 20 & 20D

 

 

300 Amp Fuse & Holder

PN# 84-4156-00

(C/R)*

300 Amp Fuse & Holder

PN# 84-4154-00

(R/R)**

300 Amp Fuse Only

PN# 84-4151-00

 

*Compression / Ring Terminal

**Ring / Ring Terminal

_

+

+ (red)

EXPLODED VIEW

OF FUSE ASSEMBLY

RING / RING TERMINAL

NUT

LOCK WASHER

FLAT WASHER

INVERTER

CABLE BATTERY CABLE

FUSE HOLDER

FUSE

WARNING

Improper stack up of hardware will cause excessive heat and fuse failure. Stack up as shown.

28

FUSE HOLDER

Part No. 90-0123-00 Libertycombi.p65 10/26/98

Image 28
Contents INVERTER/CHARGER Safety Summary Table of Contents Introduction Freedom 15 & 15D Watts Freedom 20 & 20DFreedom 15 & 15D Amps DC Freedom 20 & 20D Electronic ProtectionThings YOU should Know 15D 20DTemperature Sensitive Charging External AC Power Front Panel Controls and IndicatorsInvert Mode Charge ModeBattery Type Selection LOW Battery Red LEDStatus LEDs Operation StatusTSC Temperature Sensitive Charging LOW Battery & OVERTEMP/OVERLOADOptional Remotes Remote Control Panel Advanced Remote Control Panels Link InstrumentLink Link 2000RWet Cell Batteries Battery TypesQuality deep-cycle batteries offer good Battery Interconnection BatteriesParallel Battery Bank Ratings and SizingOnly similar batteries should be Typical Power Consumptlon AMP-HOUR Consumption FormulasBattery Charging Battery ChargingFreedom Battery Chargers Battery charger stages are Acceptance to Float Transition Points Battery Charging Battery Charging Battery Charger Voltage Settings Installation Precautions Unvented compartments containingConfirm that your shipping carton contains Typical Tools NeededInstallation Auxiliary Switch Port Jumper Grounding Neutral BondingInstallation AC WiringGround Fault Circult Interrupters DC WiringPathMaker Models Battery Cable Fusing Recommended Fuse UL Listed Class TInstallation Test the transfer functionTest the battery charger function Troubleshooting LED Status Troubleshooting Glossary LED Light Emitting Diode Indicator light Specifications Warranty Phone numbers 253