TROUBLESHOOTING

Problem

Things to Check

 

 

 

1. Battery voltage under load below 10 volts. Charge batteries.

 

2. Loose battery connections, open battery switch or blown DC fuse.

 

Tighten connections or replace fuse.

 

3. Tripped circuit breaker on front panel. Push-in to reset breaker.

No Inverter Output

4. Thermal condition, excessive loads or inadequate ventilation

caused overheating. Allow to cool. Ventilate the compartment.

 

 

5. Overloads or short circuit, check for excessive loads or shorted

 

wiring. Disconnect loads.

 

6. Check the position of the jumper in the Auxiliary Switch Port. Install

 

jumper when operating unit without a remote.

 

 

 

Confirm that your volt meter is a True RMS meter. Standard volt

Low Inverter

meters will not accurately read the waveform of the inverter and may

read anywhere from 90 to 120 volts. If a True RMS meter is not

Output Voltage

available, check the brightness of an incandescent light bulb - if it

 

 

appears normal, the output voltage is properly regulated.

 

 

 

1. Wiring - check both the AC and DC connections.

 

2. AC input voltage - low voltage input will result in low DC output

Little or No Output

current. Expect reduced charger output from generators under 3,500

from Battery

watts.

Charger

3. Check power share setting if using a remote panel.

 

4. Check the position of the jumper in the Auxiliary Switch Port if not

 

using a remote panel.

 

 

 

1. Microwave ovens will normally cook slower on inverter power

 

because the modified sine wave output has a slightly low peak AC

Microwave Oven

voltage.

Cooking Slow

2. Cooking speed will be determined by battery voltage. Low voltage

 

results in increased cooking time. Support the battery bank with an

 

alternator or other charging source for quicker cooking.

 

 

 

1. Digital clocks either employ an internal time base or derive their

 

time base from the incoming AC waveform. The inverter frequency is

Slow or Fast

well regulated at 60 Hz. The clock either counts the number of peaks

in the waveform or the number of times the waveform crosses zero

Digital Clock

volts. The circuitry that counts the zero crossing events is more

 

 

popular. The longer zero cross time of the inverter’s modified sine

 

wave may cause double clocking, resulting in a faster clock.

 

 

32

Part No. 90-0123-00 Libertycombi.p65 10/26/98

Image 32
Contents INVERTER/CHARGER Safety Summary Table of Contents Introduction Freedom 15 & 15D Watts Freedom 20 & 20DFreedom 15 & 15D Amps DC Freedom 20 & 20D Electronic ProtectionThings YOU should Know 15D 20DTemperature Sensitive Charging External AC Power Front Panel Controls and IndicatorsInvert Mode Charge ModeBattery Type Selection LOW Battery Red LEDStatus LEDs Operation StatusOptional Remotes LOW Battery & OVERTEMP/OVERLOADTSC Temperature Sensitive Charging Remote Control Panel Advanced Remote Control Panels Link InstrumentLink Link 2000RQuality deep-cycle batteries offer good Battery TypesWet Cell Batteries Battery Interconnection BatteriesOnly similar batteries should be Battery Bank Ratings and SizingParallel Typical Power Consumptlon AMP-HOUR Consumption FormulasFreedom Battery Chargers Battery ChargingBattery Charging Battery charger stages are Acceptance to Float Transition Points Battery Charging Battery Charging Battery Charger Voltage Settings Installation Precautions Unvented compartments containingConfirm that your shipping carton contains Typical Tools NeededInstallation Auxiliary Switch Port Jumper Grounding Neutral BondingInstallation AC WiringGround Fault Circult Interrupters DC WiringPathMaker Models Battery Cable Fusing Recommended Fuse UL Listed Class TInstallation Test the transfer functionTest the battery charger function Troubleshooting LED Status Troubleshooting Glossary LED Light Emitting Diode Indicator light Specifications Warranty Phone numbers 253