Panasonic FP2  Multi-wire link units,  Positioning units Rtex Network type,  S-LINK units, Cos

Page 22

XxxxxFP2/FP2SHXxxxxxxx

XxxxxSpecificationsXxxxxxxx

Multi-wire link units

Item

 

 

FP2-MW

 

Mode

W mode

 

W2 mode 1)

F mode

Communication method

Token bus

Polling

Transmission method

 

 

Base band

 

Transmission speed

500kbit/s

 

500kbit/s, 250kbit/s

500kbit/s

Transmission

 

 

Extendable to 800m

 

Extendable to 800m

 

250kbits/s: 1200m max.

Extendable to 700m

distance

 

 

 

500kbits/s: 800m max.

 

 

 

 

 

Number of

32 stations max.

1 master +

connectable stations

32 slave stations max.

 

 

 

Transmission error check

CRC (cyclic redundancy check) system

Synchronization

 

Start-stop synchronization

Interface

 

 

RS485 compatible

 

Transmission line

Twisted-pair cable

Twisted-pair cables

or VCTF cables

 

 

 

 

RAS function

Hardware self-diagnosis function

Note 1: When the unit is used in W2 mode, it must be set by user programs.

Positioning units: RTEX (Network type)

 

Item

2-axis type

4-axis type

 

8-axis type

 

Product number

FP2-PN2AN

FP2-PN4AN

 

FP2-PN8AN

 

 

Control method

PTP control, continuous path (CP) control

 

 

Interpolation control

Two/Three-axis linear interpolation, two-axis circular interpolation, three-axis helical interpolation

 

Position

Unit of control

 

Pulse/m/inch/degree

 

 

Positioning data

 

600 points per axis

 

 

control

 

 

specifications

function

Backup

Parameters and data tables can be saved in FROM

 

deceleration time

0 to 10,000ms (in increments of 1ms)

 

 

Acceleration/

Linear/S-curve acceleration and deceleration

 

 

deceleration method

 

 

 

 

 

 

 

 

Acceleration/

 

 

 

 

Unit

 

 

 

 

 

 

Positioning range

(-1073741823 to +1073741823 pulses) Increment/Absolute specification

 

Speed control function

Supported by a JOG operation (free-run operation)

 

Torque control function

Supported by a real-time torque control function

 

Home

Search method

Home proximity (DOG) search

 

return

Creep rate

 

Can be set freely

 

 

 

 

Pulser input operation supported

 

Others

 

Auxiliary output code and auxiliary output contact

 

 

 

Dwell time

 

 

 

 

 

 

 

 

 

 

In-position contact

 

specifications

Communication speed

 

100Mbps

 

Connection system

 

Ring

 

 

Cables

 

Commercially available LAN straight cable (Category 5e shielded cable)

Communication

 

 

 

 

 

 

Communication cycle/

0.5ms, 8 axes max./system (Command cycle: 1ms)

 

 

Number of connectable stations

 

 

 

 

 

 

Transmission distance

Between terminals: 60m Total: 200m

S-LINK units

Item

S-LINK units

 

CPU unit with S-LINK ports

FP2-SL2

 

FP2-C1SL

 

 

Number of channels

1

 

2

Number of I/O

128 points max.

 

128 points max. 2

The number of input and output points for each channel can be selected by the switch in the unit body

points

Input: 0/32/64/96/128 points Output: 0/32/64/96/128 points

 

Rated power

+24VDC ±10% Maximum allowable ripples (P-P): ±10%

(S-LINK terminal block IN-24VDC 1.6 A or less)

supply voltage

 

[Current consumption of the S-LINK controller (incl. D-G line current

Power

consumption)] +24VDC 1.6A or less

consumption 1)

[Maximum allowable current supply (Supply to the S-LINK and I/O

 

devices through the 24V - 0V line)] +24VDC 5A (Fuse: 5A or less)

Transmission method

Bi-directional time division multiplex transmission

Synchronization

Bit/Frame synchronization

Transmission protocol

S-LINK protocol

Transmission speed

 

28.5kbit/s

Transmission distance 2)

Main signal line: Extendable to 200m (max. 400m when a booster is used)

FAN-OUT 2)

 

320

Connection method

T-branch multi-drop wiring or standard multi-drop wiring

[+24, 0V, D-G (with a function of D-G short-circuit protection)]

 

 

 

 

 

Notes: 1) Refer to the "Power Capacity Determination" section of SUNX Limited's S-LINK Design Manual for details of the current consumption.

2) Refer to SUNX Limited's S-LINK Design Manual for the booster and FAN-OUT.

FNS (Flexible Network Slave) specifications:

Item

PROFIBUS

DeviceNet

CANopen

 

 

 

 

Baud rate

• Automatic baud rate detection

• Automatic baud rate detection

• Automatic baud rate detection

 

• 9.6 kbaud to 12Mbaud

• 125kbps to 500kbps

• 10kbps to 1Mbps

 

 

 

 

Isolation

Galvanically isolated bus electronics

Galvanically isolated bus electronics

Galvanically isolated bus electronics

 

 

 

 

Connection types

DP-V0: process data is accessed from the

• Cyclic connections

PDO (Process Data Object)

 

PROFIBUS network as cylical I/O data

• COS (Change of State)

Exchange via:

 

 

• Bit strobe connections

• Cyclic Synchronous

 

 

• Polled connections

• Acyclic Synchronous

 

 

• Explicit connections

• COS

 

 

 

Timer-driven connections

 

 

 

 

Maximum

76 words altogether for inputs and outputs

E. g. for cyclic connections:

Data 128 words

inputs / outputs

(in units of 1, 2 or 4 words)

128 words in each direction

(for TPDOs and RPDOs)

 

 

 

 

Additional features

Diagnostic support

• UCMM capable

Diagnostic support

 

 

• CIP parameter object

 

 

 

• Diagnostic support

 

 

 

 

 

22

08/2007

Image 22
Contents FP2/FP2SH Series  CPU units CPU UnitsTop Performance, Full Range of Functions  FP2  FP2SH Memory and I/O control Memory and I/O ControlFlexible Expandability  Conventional backplaneOptimal Combination with Servo Drives System configurationPositioning  Rtex positioning units Positioning units  ConfigurationHigh-Speed, High-Precision Positioning  High-speed counter units and pulse I/O units Analog control Analog ControlAccurate Process Control  Analog input units Open network NetworkingConnect all PLCs with Each Other  PLC linkFlexible Network Slave Unit Continuous Communication in Industrial ApplicationsFP Web-Server Program/Operate the PLC using an Ethernet Network Highlights Flexible Layout of I/O Devices MEWNET-F modeRemote I/O Systems  Remote I/O systems Serial communication control Serial CommunicationConnect to Various Serial Devices  Multi-communication unit MCUBasic CPUs  Features Performance specifications  Special functions  Other built-in functionsScanning time of 1ms for 20k steps Built-in comment and calendar timer functionsHigh-Performance CPUs Large programming capacity of up to 120k stepsUnit combinations Product Line and Accessories FP2/FP2SH system configurations and unit lineup Units that occupy two modules eachData hold type FP Memory LoaderData clear AFP8670FPWINPro full version supports all FP Series PLCs XxxxxControlXxxxxxxxFPWIN ProMost important highlights at a glance Free demonstration discFP OPC Server and FP Data Analyzer  Features of the FP OPC ServerOther software tools  FP OPC ServerXxxxxFP2/FP2SHXxxxxxxx XxxxxSpecificationsXxxxxxxx Power supply units ROM/EP-ROM Output units Specifications Input units OFF →ONAnalog output  Analog I/O unitsAnalog input Analog output unit FP2-DA4 ET-LAN units Performance SpecificationTransmission specifications for communication interface  Multi-communication units Positioning units Rtex Network type  Multi-wire link units FNS Flexible Network Slave specifications  S-LINK unitsFP2 Pulse I/O unit  Positioning units multifunction type pulse output typeFP2-PP21 FP2-PP41 FP2-PP22 FP2-PP42 PWM Optional memories for FP2 XxxxxProductXxxxxxxxTypes CPU units Built-in RAM  Optional memories for FP2SH I/O units  Maintenance partsProduct Types  Intelligent units for remote I/O control Other software tools  Serial communication and link-related intelligent units Fpwin Pro PLC programming software according to IEC FPWINPROFEN5L1 mm 140 209 265 349 405 L2 mm 130 199 255 339 395 DimensionsDIN rail mounting groove Mm wide DIN EN50022 L1 mm L2 mmFax 010 Please contact our Global Sales CompaniesEuen 08/07