FP2/FP2SH
Specifications
ET-LAN units
Performance Specification
Item |
| Specifications |
|
| - |
Communications function | - | |
|
| - Transparent communication |
Number of communication connections | 8 connections max. | |
Transparent | Transmit | Factory setting: 1k words/connection x 3 |
communications buffer | Receive | Factory setting: 1k words/connection x 3 |
Transmission specifications for communication interface
Item |
| 1) |
| 1) | 100BASE5 |
|
|
|
| ||
|
|
|
|
|
|
Transmission speed | 100Mbit/s |
| 10Mbit/s |
| 10Mbit/s |
Transmission method | Base band |
| Base band |
| Base band |
Max. segment length | 100m note 2) |
| 100m note 2) |
| 500m |
Max. distance between nodes | 205m (2 segments) | 500m (5 segments) | 2500m (5 segments) | ||
Communication cable or connection | Category 5 UTP cable | Category 3, 4 and 5 UTP cable | Transceiver cable | ||
Max. transceiver cable |
|
| 50m note 3) | ||
length |
|
|
|
|
|
Max. number of nodes |
|
| 100 nodes/segment | ||
Node spacing |
|
| Integer multiples of 2.5m |
Notes: 1) Switching between
2)The standards cite 100m as the maximum, but noise resistance measures such as attaching a ferrite core may be necessary in some cases, depending on the usage environment. Also, if the hub is positioned close to a control board, we recommend using it at a distance of 10m or less.
3)The standards cite 50m as the maximum, but noise resistance measures such as attaching a ferrite core may be necessary in some cases, depending on the usage environment. Also, if the transceiver is positioned close to a control board, we recommend using it at a distance of 5m or less.
Multi-communication units
|
| Computer link | 1) |
|
| |||
Item | (Panasonic open protocol "MEWTOCOL" should be used.) |
| PLC link function | |||||
|
|
| ||||||
| 1:1 communications | 1:N communications | 1:1 communications | 1:N communications |
|
|
| |
Communication |
| |||||||
block used |
| |||||||
|
|
| ||||||
Interface | RS232C RS422 | RS485 | RS232C RS422 | RS485 |
| RS232C | RS485 | |
Communication | Full duplex | Full duplex |
| Token passing | ||||
method |
| (Floating master) | ||||||
|
|
|
|
| ||||
Synchronization |
|
|
|
|
|
| ||
Transmission line |
| |||||||
or VCTF | or VCTF |
| or VCTF | |||||
|
| |||||||
Transmission distance | 15m Length: 1200m max. | Length: 1200m max. | 15m Length: 1200m max. | Length: 1200m max. |
| 1200m (RS485) 15m (RS232C) | ||
Transmission speed | 300 to 230,400bps | 300 to 230,400bps | 300 to 230,400bps | 300 to 230,400bps |
| 115,200bps | ||
(To be set in the system register) | (19,200 bps when our | (19,200 bps when our | ||||||
|
|
|
| |||||
Transmission code | ASCII, JIS7, JIS8, and binary | ASCII, JIS7, JIS8 |
|
| − | |||
|
| Data length: 7 bits/8 bits |
|
|
| − | ||
Transmission format |
| Parity: 0/Invalid/Valid (Odd/Even) |
|
|
| − | ||
| Stop bit: 1 bit/2 bits |
|
|
| − | |||
(To be set in the system register) |
|
|
|
|
| |||
Start code: With STX / Without STX | − |
|
|
| − | |||
|
|
|
| |||||
|
|
|
|
| ||||
| End code: CR/CR+LF/Time setting/ETX | − |
|
|
| − | ||
Number of stations | − | 99 stations max. | − | 99 stations max. |
| 16 stations max. | ||
(32 stations max. when our | (32 stations max. when our | |||||||
PLC link capacity | − | − | − | − |
| Link relay: 1024 points | ||
| Link register: 128 words | |||||||
|
|
|
|
|
| |||
COM1 (upper channel) | A | A | A | A |
|
| A | |
COM2 (lower channel) | A | A | A | A |
|
| N/A | |
Number of attachable units |
| 23 units max. (including 8 units for the computer link and 2 channels for the PLC link) |
|
|
| |||
Supported versions | CPU unit (both FP2 and FP2SH): Ver. 1.4 or later, FPWIN GR: Ver. 2.4 or later, FPWIN PRO: Ver. 5.1 or later |
| ||||||
Note 1: The protocol can be downloaded from: |
|
|
| A: Available | ||||
|
|
|
|
|
| N/A: Not available |
08/2007 | 21 |