Operating Instructions

6.0OPERATING INSTRUCTIONS

6.1NORMAL MODE OPERATION

During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state.

AC INPUT BATTERY UPS ON BYPASS

Normal Mode Operation at 26-50%

The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.

6.2BYPASS MODE OPERATION

Bypass mode occurs when the OFF button is pressed once while the UPS is in Normal Mode. During bypass operation, utility power

provides energy to the UPS. AC INPUT BATTERY UPS ON BYPASS The utility power bypasses

the inverter and provides

power for the connected load. Bypass Mode Operation at 26-50%

The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.

CAUTION

! Turning OFF the UPS while in bypass mode will result in loss of output power.

17

DISCONTINUED

 

PRODUCT

Image 21
Contents Liebert GXT2U DIS Product Table of Contents Tables Important Safety Instructions Product Glossary of Symbols Introduction Major Components RECTIFIER/POWER Factor Correction PFC CircuitTransient Voltage Surge Suppression Tvss EMI/RFI Filters InverterBattery Battery ChargerDC to DC Converter Dynamic BypassLiebert GXT2U, Rear View Installation Tower UPS InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS UPS External Battery Cabinet InstallationON/ALARM SILENCE/MANUAL Battery Test Button Controls and IndicatorsFault Indicator LED RED LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberBypass Indicator LED Amber Battery Indicator LED AmberOutput Voltage Selection AC Input Indicator LED GreenNormal Mode Operation Bypass Mode OperationOperating Instructions Battery Recharge Mode Battery Mode OperationCommunications Interface Port CommunicationsPins 4 & 5 Remote Shutdown on Battery Pins 5 & 6 ANY-MODE Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures Fuse Replacement AC LED TroubleshootingTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Model Rating SpecificationsGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Parameters Battery Cabinet SpecificationsBattery RUN Times Product Warranty Registration DIS Product DIS Product DIS Product Disconti Nued Product