7.2PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY

1.This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.

2.Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the command cannot be canceled.

3.A battery shutdown signal on Pin 4 will NOT cause an immediate shutdown. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.

4.If the utility returns during the 2-minute timer countdown, the shutdown timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power returns before the UPS turns OFF. This serves to reset and restart the server.

Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.

If the auto-restart is disabled, the UPS will not restart after perform- ing the 2-minute shutdown delay.

20

DISCONTINUED

 

PRODUCT

Image 24
Contents Liebert GXT2U DIS Product Table of Contents Tables Important Safety Instructions Product Glossary of Symbols Introduction RECTIFIER/POWER Factor Correction PFC Circuit Major ComponentsTransient Voltage Surge Suppression Tvss EMI/RFI Filters InverterBattery Charger BatteryDC to DC Converter Dynamic BypassLiebert GXT2U, Rear View Installation Tower UPS InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS External Battery Cabinet Installation UPSControls and Indicators ON/ALARM SILENCE/MANUAL Battery Test ButtonLOAD/BATTERY Level Indicators 4 GREEN, 1 Amber Fault Indicator LED REDBypass Indicator LED Amber Battery Indicator LED AmberAC Input Indicator LED Green Output Voltage SelectionNormal Mode Operation Bypass Mode OperationOperating Instructions Battery Mode Operation Battery Recharge ModeCommunications Communications Interface PortPins 4 & 5 Remote Shutdown on Battery Auto-Enable Output Pin 6 Logic Pins 5 & 6 ANY-MODE ShutdownUPS Intelligent Communications Configuration Program Liebert GXT2U Configuration Program AbilitiesMaintenance Battery ReplacementInternal Battery Replacement Procedures Fuse Replacement Troubleshooting AC LEDTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Specifications Model RatingGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Cabinet Specifications Battery ParametersBattery RUN Times Product Warranty Registration DIS Product DIS Product DIS Product Disconti Nued Product