Liebert gxt2u user manual Battery RUN Times

Page 39

Battery Run Times

13.0BATTERY RUN TIMES

Load% 500VA 700VA 1000VA 1500VA 2000VA 3000VA

 

10%

494

248

191

144

56

91

 

20%

181

115

87

53

33

46

 

30%

107

79

48

38

26

30

Internal

40%

83

58

34

28

19

21

50%

66

44

25

20

14

16

Battery

60%

53

35

19

15

12

11

(minutes)

70%

44

29

16

12

10

9

 

 

80%

36

24

13

10

8

8

 

90%

31

20

12

8

7

7

 

100%

28

17

11

7

6

5

 

10%

1976

992

764

576

168

364

Internal

20%

726

460

348

212

99

184

30%

431

316

192

152

78

120

Battery

40%

332

232

136

112

57

84

+ 1 External

50%

267

176

100

80

42

64

Battery

60%

210

140

76

60

36

44

Cabinet

 

 

 

 

 

 

 

70%

178

116

64

48

30

36

(minutes)

 

 

 

 

 

 

 

80%

150

96

52

40

24

32

 

90%

132

80

48

32

21

28

 

100%

115

68

44

28

18

20

 

10%

3953

1984

1528

1152

392

728

Internal

20%

1453

920

696

424

231

368

30%

862

632

384

304

182

240

Battery

40%

665

464

272

224

133

168

+ 2 External

50%

534

352

200

160

98

128

Battery

60%

421

280

152

120

84

88

Cabinets

 

 

 

 

 

 

 

70%

356

232

128

96

70

72

(minutes)

 

 

 

 

 

 

 

80%

300

192

104

80

56

64

 

90%

265

160

96

64

49

56

 

100%

231

136

88

56

42

40

 

10%

5929

2976

2292

1728

560

1092

Internal

20%

2179

1380

1044

636

330

552

30%

1293

948

576

456

260

360

Battery

40%

998

696

408

336

190

252

+ 3 External

50%

801

528

300

240

140

192

Battery

 

 

 

 

 

 

 

60%

632

420

228

180

120

132

Cabinets

 

 

 

 

 

 

 

70%

534

348

192

144

100

108

(minutes)

 

 

 

 

 

 

 

80%

450

288

156

120

80

96

 

90%

398

240

144

96

70

84

 

100%

346

204

132

84

60

60

 

10%

7906

3968

3056

2304

840

1456

Internal

20%

2906

1840

1392

848

495

736

30%

1725

1264

768

608

390

480

Battery

40%

1331

928

544

448

285

336

+ 4 External

50%

1068

704

400

320

210

256

Battery

60%

843

560

304

240

180

176

Cabinets

 

 

 

 

 

 

 

70%

712

464

256

192

150

144

(minutes)

 

 

 

 

 

 

 

80%

600

384

208

160

120

128

 

90%

525

320

192

128

105

112

 

100%

462

272

176

112

90

80

Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.

35

DISCONTINUED

 

PRODUCT

Image 39
Contents Liebert GXT2U DIS Product Table of Contents Tables Important Safety Instructions Product Glossary of Symbols Introduction Inverter RECTIFIER/POWER Factor Correction PFC CircuitMajor Components Transient Voltage Surge Suppression Tvss EMI/RFI FiltersDynamic Bypass Battery ChargerBattery DC to DC ConverterLiebert GXT2U, Rear View Installation Tower UPS InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS UPS External Battery Cabinet InstallationON/ALARM SILENCE/MANUAL Battery Test Button Controls and IndicatorsBattery Indicator LED Amber LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberFault Indicator LED RED Bypass Indicator LED AmberOutput Voltage Selection AC Input Indicator LED GreenNormal Mode Operation Bypass Mode OperationOperating Instructions Battery Recharge Mode Battery Mode OperationCommunications Interface Port CommunicationsPins 4 & 5 Remote Shutdown on Battery Pins 5 & 6 ANY-MODE Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures Fuse Replacement AC LED TroubleshootingTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Model Rating SpecificationsGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Parameters Battery Cabinet SpecificationsBattery RUN Times Product Warranty Registration DIS Product DIS Product DIS Product Disconti Nued Product