Liebert gxt2u user manual GXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120

Page 37

 

 

 

 

Specifications

SPECIFICATIONS (CONTINUED)

 

 

 

 

 

Model Number

GXT2-1500RT120

GXT2-2000RT120

GXT2-3000RT120

Model Rating

1500VA / 1050W

2000VA / 1400W

 

3000VA / 2100W

DIMENSIONS - in. (mm)

 

 

 

 

Unit

3.5 x 21.5 x 17

3.5 x 21.5 x 17

 

3.5 x 24.2 x 17

W x D x H

(87 x 547 x 430)

(87 x 547 x 430)

 

(87 x 618 x 430)

Shipping

10.6 x 27.2 x 23

10.6 x 27.2 x 23

 

10.6 x 27.2 x 23

W x D x H

(269 x 691 x 584)

(269 x 691 x 584)

 

(269 x 691 x 584)

WEIGHT - lb. (kg)

 

 

 

 

Unit

50.6 (23)

54 (24)

 

69 (31)

Shipping

59.5 (27)

62.6 (28.4)

 

78.0 (35.4)

INPUT AC PARAMETERS

 

 

 

 

Voltage Range (typical)

120 VAC nominal; variable based on output load

100% - 90% loading

90 VAC / 140 VAC

90 VAC / 140 VAC

 

90 VAC / 140 VAC

90% -70% loading

80 VAC / 140 VAC

80 VAC / 140 VAC

 

80 VAC / 140 VAC

70% -30% loading

70 VAC / 140 VAC

70 VAC / 140 VAC

 

70 VAC / 140 VAC

30% - 0% loading

60 VAC / 140 VAC

60 VAC / 140 VAC

 

60 VAC / 140 VAC

Frequency

40 -

70 Hz; Auto Sensing

 

Input Power Cord

10 ft. attached

10 ft. attached

 

10 ft. attached

w/ NEMA 5-15 plug

w/ NEMA 5-20 plug

w/ NEMA L5-30 plug

 

OUTPUT AC PARAMETERS

 

 

 

 

 

(6) 5-20R T-Slot,

 

(6) 5-20R T-Slot

Output Receptacles

(6) NEMA 5-15R

 

(1) NEMA L5-30R

accepts 15A plug

 

 

 

 

on 12 in cord

 

 

 

 

Voltage

100/110/115/120/127

(user configurable) VAC; ±3%

Frequency

 

50 Hz or 60 Hz

 

Waveform

 

Sinewave

 

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

Qty x V x Rating

4 x 12V x 7.0 or 7.2 AH

4 x 12V x 9.0 AH

 

6 x 12V x 9.0 AH

Battery Mfg / Part #

China Storage Battery/

Panasonic /

UP-VW1245P1

CSB 1270 F2

Yuasa / REW 45-12

 

Backup Time

See 13.0 - Battery Run Times

Recharge Time

5 hours to 95% capacity after full discharge into 100% load

ENVIRONMENTAL

 

 

 

 

Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000m) maximum

 

<50 dBA, at 1 meter

<55 dBA, at 1 meter

Audible Noise

from the rear

from the rear

<45 dBA, at 1 meter

<50 dBA, at 1 meter

 

 

from the front or sides

from the front or sides

AGENCY

 

 

 

 

Safety

UL 1778, c-UL Listed

 

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1A

 

33

DISCONTINUED

 

PRODUCT

Image 37
Contents Liebert GXT2U DIS Product Table of Contents Tables Important Safety Instructions Product Glossary of Symbols Introduction Major Components RECTIFIER/POWER Factor Correction PFC CircuitTransient Voltage Surge Suppression Tvss EMI/RFI Filters InverterBattery Battery ChargerDC to DC Converter Dynamic BypassLiebert GXT2U, Rear View Tower UPS Installation InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS UPS External Battery Cabinet InstallationON/ALARM SILENCE/MANUAL Battery Test Button Controls and IndicatorsFault Indicator LED RED LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberBypass Indicator LED Amber Battery Indicator LED AmberOutput Voltage Selection AC Input Indicator LED GreenBypass Mode Operation Normal Mode OperationOperating Instructions Battery Recharge Mode Battery Mode OperationCommunications Interface Port CommunicationsPins 4 & 5 Remote Shutdown on Battery Pins 5 & 6 ANY-MODE Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures Fuse Replacement AC LED TroubleshootingTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Model Rating SpecificationsGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Parameters Battery Cabinet SpecificationsBattery RUN Times Product Warranty Registration DIS Product DIS Product DIS Product Disconti Nued Product