Liebert gxt2u Major Components, Transient Voltage Surge Suppression Tvss EMI/RFI Filters

Page 9

Major Components

3.0MAJOR COMPONENTS

Input

Dynamic

Output

 

 

 

Bypass

 

L1

TVSS &

EMI/RFI

 

Filters

Rectifier

/PFC

Inverter

L1

DC to DC

 

Converter

 

Battery

Charger

L2

G

Battery

L2

G

3.1TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS)

AND EMI/RFI FILTERS

These UPS components provide surge protection and filter both elec- tromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.

3.2RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT

In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:

The utility power is used as efficiently as possible by the UPS.

The amount of distortion reflected on the utility is reduced.

This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT2U.

3.3INVERTER

In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.

5

DISCONTINUED

 

PRODUCT

Image 9
Contents Liebert GXT2U DIS Product Table of Contents Tables Important Safety Instructions Product Glossary of Symbols Introduction Major Components RECTIFIER/POWER Factor Correction PFC CircuitTransient Voltage Surge Suppression Tvss EMI/RFI Filters InverterBattery Battery ChargerDC to DC Converter Dynamic BypassLiebert GXT2U, Rear View Installation Tower UPS InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS UPS External Battery Cabinet InstallationON/ALARM SILENCE/MANUAL Battery Test Button Controls and IndicatorsFault Indicator LED RED LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberBypass Indicator LED Amber Battery Indicator LED AmberOutput Voltage Selection AC Input Indicator LED GreenNormal Mode Operation Bypass Mode OperationOperating Instructions Battery Recharge Mode Battery Mode OperationCommunications Interface Port CommunicationsPins 4 & 5 Remote Shutdown on Battery Pins 5 & 6 ANY-MODE Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures Fuse Replacement AC LED TroubleshootingTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Model Rating SpecificationsGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Parameters Battery Cabinet SpecificationsBattery RUN Times Product Warranty Registration DIS Product DIS Product DIS Product Disconti Nued Product