Emerson Figure i manual Electrical Data, Electrical data-High ambient models 105F/41C 60Hz

Page 26

Installation

2.7Electrical Data

Table 16 Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz

 

Nominal

 

Input Voltage- Phase

 

 

Capacity

* Electrical

 

 

 

 

 

 

 

 

 

Model #

Tons

Characteristic

208/230-1

208/230-3

460-3

575-3

 

 

 

 

 

 

 

 

 

FLA

8.4

 

 

 

 

 

 

 

14

1

WSA

10.2

 

 

 

 

 

 

 

 

 

OPD

15

 

 

 

 

 

 

 

 

 

FLA

12.1

 

 

 

 

 

 

 

20

1.5

WSA

14.8

 

 

 

 

 

 

 

 

 

OPD

25

 

 

 

 

 

 

 

 

 

FLA

13.5

 

 

 

 

 

 

 

27

2

WSA

16.5

 

 

 

 

 

 

 

 

 

OPD

25

 

 

 

 

 

 

 

 

 

FLA

19.3

12.8

6.4

5.9

 

 

 

 

 

 

 

37

3

WSA

23.8

15.7

7.8

7.1

 

 

 

 

 

 

 

 

 

OPD

40

25

15

15

 

 

 

 

 

 

 

 

 

FLA

15.3

7.1

6.6

 

 

 

 

 

 

 

42

3.5

WSA

18.8

8.7

8.0

 

 

 

 

 

 

 

 

 

OPD

30

15

15

 

 

 

 

 

 

 

 

 

FLA

24.1

11.7

9.1

 

 

 

 

 

 

 

67

5

WSA

29.3

14.2

11.1

 

 

 

 

 

 

 

 

 

OPD

45

20

15

 

 

 

 

 

 

 

 

 

FLA

35.6

17.4

13.5

 

 

 

 

 

 

 

96

8

WSA

40.8

19.9

15.4

 

 

 

 

 

 

 

 

 

OPD

60

25

20

 

 

 

 

 

 

 

*FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity) OPD = Overcurrent Protection Device (fuse or circuit breaker)

Table 17 Electrical data—High ambient models (105°F/41°C) 60Hz

 

Nominal

 

 

Input Voltage-Phase

 

 

Capacity,

* Electrical

 

 

 

 

 

 

 

 

 

 

 

Model #

Tons

Characteristic

208/230-1

 

208/230-3

460-3

575-3

 

 

 

 

 

 

 

 

 

 

FLA

21.3

 

14.8

7.4

5.9

 

 

 

 

 

 

 

 

37

3

WSA

25.8

 

17.7

8.8

7.1

 

 

 

 

 

 

 

 

 

 

OPD

40

 

25

15

15

 

 

 

 

 

 

 

 

 

 

FLA

 

17.3

8.1

6.6

 

 

 

 

 

 

 

 

42

3.5

WSA

 

20.8

9.7

8.0

 

 

 

 

 

 

 

 

 

 

OPD

 

30

15

15

 

 

 

 

 

 

 

 

 

 

FLA

 

24.2

11.7

9.3

 

 

 

 

 

 

 

 

67

5

WSA

 

29.4

14.2

11.3

 

 

 

 

 

 

 

 

 

 

OPD

 

50

20

15

 

 

 

 

 

 

 

 

*FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity) OPD = Overcurrent Protection Device (fuse or circuit breaker) Model # 14, 20 and 96 are not available in high ambient versions.

22

Image 26
Contents Liebert Prop Fan Condensing Unit Example PFH037A-PL7 = 380/415-3ph-50HzTable of Contents Figures Prop Fan Condensing Units Optional EquipmentEquipment Inspection Location ConsiderationsModel Numbers Dimensional Data, in. mm Lb. kg 60Hz 50Hz Dimensional DataNet Weight Cabinet and floor planning data, horizontal air dischargeFootprint Dimensions Wall Mounting Piping and Electrical Connections Electrical and piping connections, horizontal air discharge152 PFH096A- LGeneral piping arrangement Electrical field connections, 1- to 5-ton units Top Air Discharge ModelsElectrical field connections, 8-ton units Single-phase, 1-3 ton model schematic, typical Three-phase, 3-5 ton model schematic, typical Three-phase, 8 ton model schematic, typical Piping Considerations Piping for Elevation Differences between PFH and EvaporatorEquivalent lengths for various pipe fittings, ft m EvaporatorCondensing Unit Refrigerant charge in Liebert pre-charged R-407C line sets Pre-Charged Line SetsField-Fabricated Line Sets Line Size Length Charge R-407C Ft. m Lb-oz kgLiebert PFH unit charge levels and coupling size Recommended line sizes, OD CuLine charges refrigerant per 100 ft m of Type L copper tube Installation of Piping to UnitsPiping connection sizes and torque Line Size OD Cu Coupling Size Torque, lb-ft. N-mRemove Existing Condensing Unit Filter Drier Selection and InstallationInstall the New Condensing Unit Evaporator Charge R-407C Indoor Unit Models Oz kg General System Charge RequirementsEvaporator Charge Levels Electrical Connections Low-Voltage Control Wire ConnectionsLow-Voltage Control Wire Sizing Electrical Data Nominal Input Voltage- Phase Capacity ElectricalNominal Input Voltage-Phase Capacity Electrical Electrical data-High ambient models 105F/41C 60HzElectrical data-Quiet-Line models 95F/35C 60Hz Electrical data-High ambient models 105F/41C 50HzChecklist for Completed Installation Electrical data Quiet-Line models 95F/35C 50HzLiebert Lee-Temp Flood Back Head Pressure Control CompressorHigh Head Pressure Operation AdjustmentHot Gas Bypass Hot gas bypass diagram Electrical Failure-Burnout GeneralCompressor Failure Mechanical FailureCompressor Replacement Model Numbers 407C 60 Hz 50 Hz Oz kg Field Charge VerificationField verification charge Troubleshooting Problem Cause RemedyUni Single-Phase&Three-Phase UPS Environmental SystemsWeb Site Monitoring Etwo