Emerson MRLDS Mrlds Setup, Mrlds Wiring, Rmcc Controllers, Mrlds Network Addressing

Page 11

4.2MRLDS Setup

4.2.1MRLDS Wiring

MODBUS

MRLDS - INSIDE LOWER

PORTION OF BASE

To Gateway

 

 

Board

Figure 3-4- Analog Input Screen Settings Example for E2

3.4.3RMCC Controllers

For RMCC-type controllers, set the Gain parameter to 250 and Offset to -1000.

) )

D

 

NG

 

-

+

 

(

 

 

(

 

485

5

 

ARHTE ACN 24VAC

8

4

S

 

R

 

RS

 

 

 

14 AWG less

MODBUS

 

than 6 inches

NETWORK Shield

 

BELDEN

drain/ground

 

8761

wire

 

 

 

 

A transformer must never be shared between MRLDS and the Gateway board. A separate transformer must be used.

If a transformer is shared between MRLDS units, the “ACN” of each MRLDS must be wired to the same phase of the transformer.

4MRLDS Modbus Version (809-101x)

4.1Network Layout

E2

 

 

 

+

 

 

 

-

I/O Net

 

 

 

 

- +

 

 

 

Gateway

 

 

 

 

+

MRLDS

 

 

-

 

 

+

MRLDS

MODBUS

-

 

+

 

MRLDS

-

 

 

+

 

 

MRLDS

 

 

-

 

 

(Up to 12 MRLDS units on the network per Gateway)

Figure 4-1- Network Layout Example

Figure 4-2- Modbus MRLDS Wiring

4.2.2MRLDS Network Addressing

Modbus network settings are set on jumpers J5, J4, and J3. Refer to Table 4-1(also included on the inside label of the MRLDS) for network addressing with corre- sponding jumper settings.

If more than one MRLDS is on the network, each unit must have a unique address and be numbered according to the inside label (Table 4-1) specifications.

J6 J1

J6 J5 J4 J3 J2 J1

term

network

refrigerant

jumper

address

type

 

jumpers

jumpers

Figure 4-3- MRLDS Jumpers (Inside Lower Portion of Cover)

Network Layout

MRLDS Modbus Version (809-101x) 5

Image 11
Contents Rev 1 Page FCC Compliance Notice Page Table Of Contents Page Mrlds Models SpecificationsPowering The Mrlds Mounting The Sensor Choosing a Mounting LocationNetwork Layout Mrlds DimensionsMrlds Wiring Refrigerant Type J2J1 Refrigerant Jumper SettingsController Setup For Analog Mrlds 1 E2 Controllers Version 2.5 and NewerMrlds Network Addressing Mrlds SetupMrlds Wiring Rmcc ControllersMrlds Termination Address SettingsRefrigerant Jumper Settings Modbus Address J5J4J3 Jumper SettingsGateway Board Mrlds Gateway Setup on I/O NetworkMrlds Gateway Gateway ConnectionsThree-Board Six-Board Powering the Gateway BoardWire Connections Input VoltageGateway Board I/O Net Addressing Termination SettingsSelect Screen Setting the Baud Rate Dip SwitchesMrlds Setup Hand-Held Terminal Set TingsDesignating Mrlds as a 16AI Board Controller Setup for Modbus MrldsGateway Troubleshooting Mapping The Mrlds as an Irlds ApplicationPress 2 to Set Device #’s Reflecs Setup for Irlds IIs3 E2/Einstein Controllers Rmcc Controllers Version 2.1 and NewerSensor Setpoints Sensor SetupInput Definitions Alarm Setpoints E2 AlarmingIrlds Mode 2 16AI Mode