Emerson MRLDS operation manual Choosing a Mounting Location, Mounting The Sensor

Page 8

If a transformer is shared between MRLDS units, the “ACN” of each MRLDS must be

wired to the same phase of the transformer.

 

 

 

r

24VAC

 

 

 

e

 

120VAC

 

rm

 

 

s

 

 

 

 

fo

 

 

 

 

n

 

 

 

ra

 

ACN

 

T

 

 

 

 

 

 

 

MRLDS I

MRLDS II

Figure 1-2- Powering Multiple MRLDS Units

2Choosing a Mounting Location

Proper location of the refrigerant sensor is necessary to ensure accurate measurement of representative air sam- ples.

Mount the sensor:

Indoors, inside a room area where air circulates freely.

On a flat, interior surface.

Approximately 12-18 inches (30-45 cm) from the floor.

Do not mount the sensor:

On surfaces in unheated areas (less than 0°C), unless using a model with a de-icer.

Near heat sources, such as appliances, direct sunlight, or concealed pipes or chimneys.

On walls subject to excessive vibration.

In the direct path of an exhaust fan. Excessive air movement will disperse gas before it can be detected. If mounting in the path of excessive airflow cannot be avoided, it will be necessary to turn OFF air circulation for 1/4 to 1/2 hour, 4-6 times a day.

NOTE: For example, if mounted inside a motor room, exhaust fans must be shut off during the intervals that air samples will be tested for

refrigerant levels.

Figure 2-1- Sensor Base And Cover

2.1Mounting The Sensor

The refrigeration monitor comprises two basic parts: the base and the cover. The cover incorporates the circuit board with the sensing elements.

1.Fasten the base to a junction box or other support. The base has a number of openings to allow for mounting to various junction boxes.

2.Feed the power and signal wires through the rect- angular opening in the base (Figure 1-1).

3.Connect the wires to the terminal connector located in the base, as indicated in Figure 4-2and Figure 3-2.

4.The Modbus MRLDS must be connected to earth ground. Connect earth ground to the MRLDS

ground terminal labeled . Connect to earth ground with 14 AWG wire that is less than 6 inches.

5.Align the two side tabs of the cover with the base and snap the cover onto the base.

6.Verify the cover is securely attached to the base by pulling on the top and bottom of the cover as shown in Figure 2-2.

NOTE: To remove the cover, grasp it along the recesses and pull it away from the base (Figure 2-2). Alternatively, place a screwdriver into the

slots indicated in Figure 2-2and twist.

2 MRLDS I&O Manual

026-1307 Rev 1 11-30-07

Image 8
Contents Rev 1 Page FCC Compliance Notice Page Table Of Contents Page Mrlds Models SpecificationsPowering The Mrlds Choosing a Mounting Location Mounting The SensorNetwork Layout Mrlds DimensionsMrlds Wiring Refrigerant Jumper Settings Controller Setup For Analog Mrlds1 E2 Controllers Version 2.5 and Newer Refrigerant Type J2J1Mrlds Setup Mrlds WiringRmcc Controllers Mrlds Network AddressingAddress Settings Refrigerant Jumper SettingsModbus Address J5J4J3 Jumper Settings Mrlds TerminationMrlds Gateway Setup on I/O Network Mrlds GatewayGateway Connections Gateway BoardPowering the Gateway Board Wire ConnectionsInput Voltage Three-Board Six-BoardTermination Settings Gateway Board I/O Net AddressingSetting the Baud Rate Dip Switches Mrlds SetupHand-Held Terminal Set Tings Select ScreenController Setup for Modbus Mrlds Gateway TroubleshootingMapping The Mrlds as an Irlds Application Designating Mrlds as a 16AI BoardReflecs Setup for Irlds IIs 3 E2/Einstein ControllersRmcc Controllers Version 2.1 and Newer Press 2 to Set Device #’sSensor Setpoints Sensor SetupInput Definitions E2 Alarming Irlds Mode2 16AI Mode Alarm Setpoints