Emerson MRLDS Powering the Gateway Board, Wire Connections, Input Voltage, Three-Board Six-Board

Page 14

CAUTION: Before installing the Gateway board, verify the jumper JP7 (located near the top center of the board) is set to the “NOR-

MAL” position (not the “TEST” position). Operating the Gateway with the jumper in “TEST” position may cause board damage.

The Gateway Board communicates with the MRLDS via the Modbus network, which is connected to the Gate- way’s “Receiver Bus” network terminal. The Gateway communicates with the E2 via the RS485 I/O Network.

4.3.4Powering the Gateway

Board

Input Voltage

24VAC, Class 2, Center-Tapped

 

50/60Hz

 

 

Power

5VA

Table 4-4- Gateway Power Requirements

The Gateway board requires 24VAC power from a Class 2 center-tappedtransformer. CPC supplies several sizes of center-tapped transformers for powering multiple 16AIs, 8ROs, and other RS485 peripheral boards.

Figure 4-8shows how to connect the 56VA and 80VA transformers to the Gateway power connector.

 

Three-Board

Six-Board

 

 

 

P/N

640-0056

640-0080

 

 

 

Power Rating

56 VA

80 VA

 

 

 

Table 4-5- Power Ratings for CPC Transformers

Figure 4-8- Pinout for the 56VA (640-0056) and 80VA (640-

0080) Transformers

CAUTION: The MRLDS unit requires a sepa- rate Class 2, 24VAC, 10VA power supply.

4.3.5Connecting the Gateway Board to the Einstein or REFLECS Network

Each E2, Einstein, or REFLECS site controller that will communicate with one or more MRLDS units must have a Gateway Board installed on its RS485 I/O Net- work. For Einstein controllers, this means the Gateway will be installed on the RS485 I/O Network; for RMCC, BEC, BCU, and other REFLECS products, the Gateway will be installed on the COM A or COM D network.

4.3.6Wire Connections

Using shielded three-conductor network cable (Belden #8641 or equivalent), connect the RS485 I/O Network wire to the three-terminal connector on the Gateway board as shown in Figure 4-9. For further information about how RS485 networks are configured, refer to your site

8 MRLDS I&O Manual

026-1307 Rev 1 11-30-07

Image 14
Contents Rev 1 Page FCC Compliance Notice Page Table Of Contents Page Mrlds Models SpecificationsPowering The Mrlds Choosing a Mounting Location Mounting The SensorNetwork Layout Mrlds DimensionsMrlds Wiring 1 E2 Controllers Version 2.5 and Newer Refrigerant Jumper SettingsController Setup For Analog Mrlds Refrigerant Type J2J1Rmcc Controllers Mrlds SetupMrlds Wiring Mrlds Network AddressingModbus Address J5J4J3 Jumper Settings Address SettingsRefrigerant Jumper Settings Mrlds TerminationGateway Connections Mrlds Gateway Setup on I/O NetworkMrlds Gateway Gateway BoardInput Voltage Powering the Gateway BoardWire Connections Three-Board Six-BoardTermination Settings Gateway Board I/O Net AddressingHand-Held Terminal Set Tings Setting the Baud Rate Dip SwitchesMrlds Setup Select ScreenMapping The Mrlds as an Irlds Application Controller Setup for Modbus MrldsGateway Troubleshooting Designating Mrlds as a 16AI BoardRmcc Controllers Version 2.1 and Newer Reflecs Setup for Irlds IIs3 E2/Einstein Controllers Press 2 to Set Device #’sSensor Setpoints Sensor SetupInput Definitions 2 16AI Mode E2 AlarmingIrlds Mode Alarm Setpoints