Emerson MRLDS operation manual Gateway Board I/O Net Addressing, Termination Settings

Page 15

controller’s user manual.

GATEWAY BOARD

-485

0v

+485

Figure 4-9- Connecting the Gateway to the E2 RS485 Network

To connect the Gateway to an MRLDS, feed the wires through the rectangular opening in the sensor base as indi- cated in Figure 1-1. Locate the RS485 connector and secure the wire leads to the connector orienting them as shown in Figure 4-10. Connect multiple MRLDS units in a daisy-chain configuration as shown in Figure 4-1.

 

RS485 I/O NET

 

TERM JUMPERS

TERMINATION

RS485

 

I/O NET

(ALWAYS

(TO CPC

CONTROLLER)

TERMINATE)

 

Figure 4-11-MRLDS Gateway Termination

4.3.8Gateway Board I/O Net Addressing

Set the address on the I/O Network with switches 1-4. There can be more than one MRLDS Gateway with each supporting up to 12 MRLDS units.

GATEWAY BOARD

MRLDS - INSIDE LOWER

PORTION OF BASE

A B

DNG

-

+

 

485

5

ARTHE ACN 24VAC

8

4

S

RS

R

MODBUS

Shield

drain/ground

NETWORK

 

 

wire

To MRLDS

MODBUS

-485 0v

+485 Shield drain/ ground wire

-485

0v +485

Switch 5 indicates whether the MRLDS will be mapped as an IRLDS or 16AI. Set switch 5 to the OFF position for IRLDS emulation or to the ON position for 16AI emulation.

I/O NET MODE

ON = 16AI

OFF = IRLDS

Figure 4-10- Connecting the Gateway to MODBUS

4.3.7Termination Settings

As part of a site controller’s RS485 I/O (COM A or COM D) Network, a Gateway must be terminated if it is the end device of a daisy chain. The Gateway on the Mod- bus Network should always be terminated and always located at the end of the daisy chain.

Refer to the site controller’s user manual for informa- tion about daisy chain networks and how they are termi- nated.

To terminate the Gateway (the Modbus jumpers should always be terminated on the Gateway), set the receiver bus jumpers to the RIGHT position (Figure 4-11).

ADDRESS ON

 

I/O NET

 

14

15

Figure 4-12- Network Layout Example

MRLDS Gateway

MRLDS Modbus Version (809-101x) 9

Image 15
Contents Rev 1 Page FCC Compliance Notice Page Table Of Contents Page Specifications Powering The MrldsMrlds Models Mounting The Sensor Choosing a Mounting LocationMrlds Dimensions Mrlds WiringNetwork Layout Refrigerant Type J2J1 Refrigerant Jumper SettingsController Setup For Analog Mrlds 1 E2 Controllers Version 2.5 and NewerMrlds Network Addressing Mrlds SetupMrlds Wiring Rmcc ControllersMrlds Termination Address SettingsRefrigerant Jumper Settings Modbus Address J5J4J3 Jumper SettingsGateway Board Mrlds Gateway Setup on I/O NetworkMrlds Gateway Gateway ConnectionsThree-Board Six-Board Powering the Gateway BoardWire Connections Input VoltageGateway Board I/O Net Addressing Termination SettingsSelect Screen Setting the Baud Rate Dip SwitchesMrlds Setup Hand-Held Terminal Set TingsDesignating Mrlds as a 16AI Board Controller Setup for Modbus MrldsGateway Troubleshooting Mapping The Mrlds as an Irlds ApplicationPress 2 to Set Device #’s Reflecs Setup for Irlds IIs3 E2/Einstein Controllers Rmcc Controllers Version 2.1 and NewerSensor Setup Input DefinitionsSensor Setpoints Alarm Setpoints E2 AlarmingIrlds Mode 2 16AI Mode