Emerson MRLDS operation manual Specifications, Mrlds Models, Powering The Mrlds

Page 7

1 Overview

CPC specs a modular refrigerant leak detection sensor (MRLDS) that continuously monitors for low levels of refrigerants most commonly used in commercial refrigera- tion systems.

The MRLDS communicates with the E2 controller via a Gateway board connected to the RS485 I/O Network, or via the analog input on a MultiFlex board.

1.1Specifications

 

Power Require-

 

24 VAC, ±20%, 50/60 Hz, Class 2

 

ments

 

 

 

Wiring

 

14 AWG max, Class 2 copper wir-

 

 

 

ing

 

Power Consump-

 

Less than 2.7 watts

 

tion

 

 

 

Output Options

 

1-5V, 10 K Ohm load

 

 

 

RS485 Modbus RTU

 

Operating Temp.

 

32 to 149°F (-22 to 149°F with

 

 

 

de-icer*)

 

 

 

0 to 65°C (-30 to 65°C with

 

 

 

de-icer*)

 

Humidity

 

0 to 99% non-condensing

 

Size

 

4.5” x 3.5” x 1.6”

 

Weight

 

.35 lbs. (160 g)

 

Pollution Degree

 

2

 

Installation Cate-

 

II

 

gory

 

 

 

Range

 

0 to 1000 ppm

 

Minimum Detec-

 

25 ppm

 

tion

 

 

 

Pressure

 

Operating 10.2 to 15.7 PSIA

 

Repeatability

 

±10 ppm at 50 ppm

 

Linearity

 

±10 ppm from 25-50 ppm,

 

 

 

±20% of reading from 60 to 1000

 

 

 

ppm

 

Warm-up Time

 

30 minutes

 

 

 

 

Table 1-1- MRLDS Unit Specifications

*De-icer: for environments below 32°F to keep ice from forming on the surface of enclosure.

Figure 1-1- Sensor Base Opening With Screw Terminals

1.2MRLDS Models

Part Number

Description

 

 

809-1000

Voltage Out w/o de-icer*

 

 

809-1001

Voltage Out w/ de-icer*

 

 

809-1010

Modbus w/o de-icer*

 

 

809-1011

Modbus w/ de-icer*

 

 

Table 1-2- Available MRLDS Models

1.3Powering The MRLDS

Part Number

Transformer

Number of

 

Description

MRLDS Units

 

 

Powered

640-0039

24VAC, 10VA

Up to 3

 

Class 2

 

Table 1-3- MRLDS Transformer Specifications

The MRLDS unit requires a separate UL Listed/CSA Certified 24VAC Class 2 transformer power supply. One 24VAC, 10VA Class 2 transformer is sufficient for up to three (3) MRLDS units.

CPC supplies several sizes of transformers for power- ing multiple MRLDS units (three or more). Note that polarity must be maintained when connecting more than one MRLDS to a single transformer.

WARNING: The MRLDS unit must be always be powered by either a suitable UL 60950/CSA Certified power supply that is isolated from line voltage by double insulation, or an appropriately rated

UL Listed/CSA Class 2 transformer. Failure to follow the above can result in serious personal injury or death.

Specifications

Overview 1

Image 7
Contents Rev 1 Page FCC Compliance Notice Page Table Of Contents Page Powering The Mrlds SpecificationsMrlds Models Mounting The Sensor Choosing a Mounting LocationMrlds Wiring Mrlds DimensionsNetwork Layout Refrigerant Type J2J1 Refrigerant Jumper SettingsController Setup For Analog Mrlds 1 E2 Controllers Version 2.5 and NewerMrlds Network Addressing Mrlds SetupMrlds Wiring Rmcc ControllersMrlds Termination Address SettingsRefrigerant Jumper Settings Modbus Address J5J4J3 Jumper SettingsGateway Board Mrlds Gateway Setup on I/O NetworkMrlds Gateway Gateway ConnectionsThree-Board Six-Board Powering the Gateway BoardWire Connections Input VoltageGateway Board I/O Net Addressing Termination SettingsSelect Screen Setting the Baud Rate Dip SwitchesMrlds Setup Hand-Held Terminal Set TingsDesignating Mrlds as a 16AI Board Controller Setup for Modbus MrldsGateway Troubleshooting Mapping The Mrlds as an Irlds ApplicationPress 2 to Set Device #’s Reflecs Setup for Irlds IIs3 E2/Einstein Controllers Rmcc Controllers Version 2.1 and NewerInput Definitions Sensor SetupSensor Setpoints Alarm Setpoints E2 AlarmingIrlds Mode 2 16AI Mode