Emerson Process Management T-SERIES Maximum wiring distances, Maximum cable lengths, Pipe run

Page 8

Determining a Location

Maximum wiring distances

If the transmitter is mounted remotely from the sensor, the maximum distance between the sensor and transmitter depends on cable type. See Table 2.

Table 2 Maximum cable lengths

Cable type

 

Wire size

Maximum length

Micro Motion 9-wire to an MVD transmitter

 

Not applicable

60 feet (20 meters)

or core processor

 

 

 

 

 

 

 

 

Micro Motion 9-wire to all other transmitters

Not applicable

1000 feet (300 meters)

 

 

 

 

Micro Motion 4-wire

Not applicable

1000 feet (300 meters)

 

 

 

 

 

User-supplied 4-wire(1)

 

 

 

 

Power wires (VDC)

22

AWG (0,35 mm2)

300 feet (90 meters)

 

 

 

 

 

 

20

AWG (0,5 mm2)

500 feet (150 meters)

 

 

 

 

 

 

18

AWG (0,8 mm2)

1000 feet (300 meters)

 

 

 

 

 

Signal wires (RS-485)

22

AWG (0,35 mm2) or larger

1000 feet (300 meters)

 

 

 

 

 

(1) Micro Motion recommends using Micro Motion cable.

Pipe run

Micro Motion sensors do not require a straight run of pipe upstream or downstream.

Valves

After the sensor and transmitter have been installed, you must perform the zeroing procedure. During the zeroing procedure, flow through the sensor must be halted and the sensor tubes must be completely full of process fluid. A shutoff valve, downstream from the sensor, is recommended to halt flow during the zeroing procedure. For more information about zeroing, refer to the instruction manual shipped with the transmitter.

6

Image 8
Contents Micro Motion Series Sensor Page Customer service TroubleshootingSpecifications Before You BeginEuropean installations Installation optionsDefinitions Purge plugsSeries sensor with core processor Hazardous area installations Determining a LocationFull flow tubes Environmental limitsSeries sensor ambient and process temperature limits UL and CSA ambient temperature limitsMaximum wiring distances Maximum cable lengthsPipe run ValvesHygienic applications Orienting the SensorSelf-draining applications Eccentric reducer Flow direction arrowMounting the Sensor Mounting a T-Series sensorWiring Core processor to a 4-wire remote transmitterWrapping the shield drain wires Applying the heat shrink Connecting the wires at the core processor Case purging procedure GroundingPurge Fittings Removing a purge plugTime required to purge T-Series sensor cases Purge rate Time Sensor modelUsed equipment Return PolicyNew and unused equipment Page 20002172