Sierra Monitor Corporation 4105 Installation, Sensor Locations, Sensor Mounting, Power Supply

Page 11

Instruction Manual

7.INSTALLATION

7.1 Sensor Locations

Select locations for each of the sensors based on the following:

-Consider the density of the gas to determine height of sensor above floor or ground level.

-Sensors should be placed close to the potential source of gas.

-Sensors should be placed in areas accessible for calibration.

-Sensors must be pointed down and the conduit should include an inverse trap to reduce mois- ture (condensation) from accumulating in the elec- tronics enclosure. See Figure 7.1.

7.2Sensor Mounting

Where possible sensor modules should be installed with the sensor facing vertically down. The lid of the sensor module should face out for easy access.

Sensors may be mounted directly onto the end of a vertical conduit, or bracketed to a vertical surface us- ing the two mounting flanges. Insure that the body of the enclosure is at least 1" from the wall so that the sensor assembly can be rotated for removal and re- placement. See Figure 6.1 for installation configura- tions.

7.3 Explosion Proof Installation

Where area classification requires explosion proof (NEMA-7) installation a sealing fitting will be required immediately above the gas sensor module enclosure.

7.4 Power Supply

The power supplied by the controlling device or an external power supply must meet the following speci- fications:

Voltage:

21-30 VDC

Current:

180 mA (Combustibles)

 

40 mA (Oxygen & Toxics)

Figure 7.1

Gas Sensor Module Installation

Page: 8

Model 4105 Gas Sensor Module (12/02)

Image 11
Contents Model 4105 Series Applicability & Effectivity Table of Contents Section Product Description Preventative Maintenance Introduction WiringWire Gauge Maximum Length Recommended Wire/Cable GaugeQuick Start Transmitter Cover Plate Model 4105 Gas Sensor Module 12/02 OperationCalibration Service 4c Electrochemical Oxygen and Toxics 4b LEL Sensor Fault Supervision4d Missing Electromechanical Sensor Fault Supervision 4a. CombustiblesSensor Locations InstallationExplosion Proof Installation Power SupplyToxics Oxygen Wiring Diagram Model 4105 Gas Sensor Module 12/02Combustible Specifications Sensor Type Units Range Resolution Response TimeHCN Limitedwarranty Replacement PartsAppendix C End of Sensor Life Indication Appendix a Unity Gain ModeAppendix B L.C.D. Readout Calibration Procedure Appendix C Combustible Gas Scaling Factors Table Factor Combustible GAS Scaling Factors