AEG PV 2000 operating instructions Installation Instructions, Before Installation

Page 11

11

3. INSTALLATION INSTRUCTIONS

OPENING THE PACKAGE

After opening the package, please check the contents of the box. It should contain the following:

1.One Protect PV inverter

2.Instruction manual

3.One mounting frame

4.4 mounting screws

5.2 safety-lock screws

6.One AC socket assembly for Protect PV 2000 and 2800

BEFORE Installation

Before starting installation please consider the following items: This unit is designed for indoor usage. Do not expose the unit to wet, or moist conditions.

Do not expose the PV-Inverter to direct sunlight. Direct sunlight increa- ses the internal temperature that may reduce conversion efficiency.

Check the ambient temperature of installation is within specified range of -20 ~ +55 °C.

The AC grid voltage is between 196 and 253VAC, 50/60Hz.

Electric utility company has approved the grid connection.

Qualified personnel are performing the installation.

Adequate convection space surrounds the inverter.

Inverter is being installed away from explosive vapors.

No flammable items are near the inverter.

Protect PV can be installed and operated at locations where the am- bient temperature is up to 55°C. However, for optimal operation, it is recommended that Protect PV is installed where the ambient tempera- ture is between 0~40°C.

Image 11
Contents DOC n 07/08/1002-2 Rev Protect pV 2000Contents BEFORe you start Risk of electric shock Safety instructionsTerms of warranty Limited warrantyWarranty claims procedure Exclusions Warranty extension Protect PV 2000 OverviewFeatures Before Installation Installation InstructionsMounting Protect PV to the wall Page Connecting to the grid AC utility Page Checking Connect to PV Panel DC inputSySTEm diagRam Front Panel Operating Your PV-InverterModes of operation Page Accuracy of the readinG Maximum power point trackinG mpptDisplay information Inverter StatusERR Grid ERR Ground FaultOvertemperature ERR IsolationLCD Locked Model PVContrast SET ContrastCOmmuNiCaTiONS Page Display Trouble shootingLow DC Bus DC Input SpecificationsModell Typical Efficiency charts vs. Load Compliance & Standards Regulation & CertificatesIncident Form Page Operating Instructions