AEG PV 2000 operating instructions Operating Your PV-Inverter, Modes of operation, Front Panel

Page 18

18

5. Operating Your PV-Inverter

Modes of operation

There are 3 different modes of operation.

1.Normal mode: In this mode, Protect PV works normally. Whenever the supplied power from PV panel is sufficient (voltage>150VDC),

Protect PV converts power to the grid as generated by the PV panel. If the power is insufficient, (voltage<120VDC) Protect PV enters a “waiting” state. Whilst “waiting” Protect PV uses just enough power from the PV panel monitor internal system status. In normal mode the green LED is on.

2.Fault mode: The internal intelligent controller can continuously monitor and adjust the system status. If Protect PV finds any unex- pected conditions such as grid problems or internal failure, it will display the information on its LCD and light up the red “Fault” LED.

3.Shutdown mode: During periods of little or no sunlight, Protect PV automatically stops running. In this mode, Protect PV does not take any power from the grid. The display and LED’s on the front panel do not work.

Front Panel

Operating Protect PV is quite easy. During normal operation, Protect PV runs automatically. However, to achieve maximum conversion efficiency of Protect PV please read the following information:

1.Automatic ON-OFF: Protect PV starts up automatically when DC-power from the PV panel is sufficient. Once the PV-Inverter starts it enters one of the following 3 states:

Standby: The PV string can only provide just enough voltage to minimum requirements of the controller.

Waiting: When the PV string DC voltage is greater than 100V, Protect PV enters a “waiting” state and attempts to connect to the grid.

Image 18
Contents Protect pV 2000 DOC n 07/08/1002-2 RevContents BEFORe you start Safety instructions Risk of electric shockLimited warranty Terms of warrantyWarranty claims procedure Exclusions Warranty extension Overview Protect PV 2000Features Installation Instructions Before InstallationMounting Protect PV to the wall Page Connecting to the grid AC utility Page Connect to PV Panel DC input CheckingSySTEm diagRam Operating Your PV-Inverter Modes of operationFront Panel Page Maximum power point trackinG mppt Accuracy of the readinGInverter Status Display informationERR Isolation ERR Ground FaultOvertemperature ERR GridSET Contrast Model PVContrast LCD LockedCOmmuNiCaTiONS Page Trouble shooting DisplayLow DC Bus Specifications ModellDC Input Typical Efficiency charts vs. Load Regulation & Certificates Incident FormCompliance & Standards Page Operating Instructions