26
8. Trouble shooting
System Fault
In most situations, the Protect PV inverter requires very little service. However, if Protect PV is not able to work perfectly, please refer to the following instructions before calling your local AEG PS dealer.
•Should any problems arise, the red (Fault) LED on the front panel turns on and the LCD displays the relevant information. Please refer to the following table for a list of potential problems and their solutions.
DISPLAY | Possible actions | ||
| 1. | Check the impedance is between PV (+) & PV | |
Isolation Fault |
| Inverter is earthed. The impedance must be greater than 8M | |
| 2. | If the problem persists please call service | |
| 1. | The ground current is too high. | |
| 2. | Unplug the inputs from the PV generator and check the | |
Ground I Fault |
| peripheral AC system | |
3. | After the cause is cleared, | ||
| |||
|
| ||
| 4. | If the problem persists please call service. | |
| 1. | Wait for 5 minutes, if the grid returns to normal, | |
Grid Fault |
| automatically restarts. | |
2. | Make sure grid voltage and frequency meet the specifications | ||
| |||
| 3. | If the problem persists please call service | |
| 1. | Grid impedance higher than the permissible value. | |
| 2. | Wait for 5 minutes, see if it works again. | |
Impedance Fault | 3. | Check the wires between the | |
| larger wires if necessary. | ||
|
| ||
| 4. | Adjust impedance parameter by Protect PV Data program. | |
| 5. | If the problem persists please call service | |
| 1. | Grid is not connected. | |
No Utility | 2. Check grid connection cables. | ||
| 3. | Check grid usability. |