AEG PV 2000 operating instructions Trouble shooting, Display

Page 26

26

8. Trouble shooting

System Fault

In most situations, the Protect PV inverter requires very little service. However, if Protect PV is not able to work perfectly, please refer to the following instructions before calling your local AEG PS dealer.

Should any problems arise, the red (Fault) LED on the front panel turns on and the LCD displays the relevant information. Please refer to the following table for a list of potential problems and their solutions.

DISPLAY

Possible actions

 

1.

Check the impedance is between PV (+) & PV (-) and the PV-

Isolation Fault

 

Inverter is earthed. The impedance must be greater than 8M

 

2.

If the problem persists please call service

 

1.

The ground current is too high.

 

2.

Unplug the inputs from the PV generator and check the

Ground I Fault

 

peripheral AC system

3.

After the cause is cleared, re-plug the PV panel and check

 

 

 

PV-Inverter status.

 

4.

If the problem persists please call service.

 

1.

Wait for 5 minutes, if the grid returns to normal, PV-Inverter

Grid Fault

 

automatically restarts.

2.

Make sure grid voltage and frequency meet the specifications

 

 

3.

If the problem persists please call service

 

1.

Grid impedance higher than the permissible value.

 

2.

Wait for 5 minutes, see if it works again.

Impedance Fault

3.

Check the wires between the PV-Inverter and grid. Replace with

 

larger wires if necessary.

 

 

 

4.

Adjust impedance parameter by Protect PV Data program.

 

5.

If the problem persists please call service

 

1.

Grid is not connected.

No Utility

2. Check grid connection cables.

 

3.

Check grid usability.

Image 26
Contents Protect pV 2000 DOC n 07/08/1002-2 RevContents BEFORe you start Safety instructions Risk of electric shockLimited warranty Terms of warrantyWarranty claims procedure Exclusions Warranty extension Overview Protect PV 2000Features Installation Instructions Before InstallationMounting Protect PV to the wall Page Connecting to the grid AC utility Page Connect to PV Panel DC input CheckingSySTEm diagRam Front Panel Operating Your PV-InverterModes of operation Page Maximum power point trackinG mppt Accuracy of the readinGInverter Status Display informationERR Isolation ERR Ground FaultOvertemperature ERR GridSET Contrast Model PVContrast LCD LockedCOmmuNiCaTiONS Page Trouble shooting DisplayLow DC Bus DC Input SpecificationsModell Typical Efficiency charts vs. Load Compliance & Standards Regulation & CertificatesIncident Form Page Operating Instructions