10-11. Selecting Extension Cord (Use Shortest Cord Possible)

Cord Lengths for 120 Volt Loads

YIf unit does not have GFCI receptacles, use GFCI-protected extension cord.

 

 

 

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

 

Current

 

 

 

 

 

 

 

 

 

 

 

Load (Watts)

4

 

 

6

 

8

10

12

 

14

(Amperes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

 

 

 

 

350

(106)

225 (68)

137 (42)

 

100 (30)

 

 

 

 

 

 

 

 

 

 

 

7

840

 

 

400

(122)

250 (76)

150 (46)

100 (30)

 

62 (19)

 

 

 

 

 

 

 

 

 

 

10

1200

400 (122)

 

275 (84)

175 (53)

112 (34)

62 (19)

 

50 (15)

 

 

 

 

 

 

 

 

 

 

15

1800

300 (91)

 

175 (53)

112 (34)

75 (23)

37 (11)

 

30 (9)

 

 

 

 

 

 

 

 

 

 

 

20

2400

225 (68)

 

137 (42)

87

(26)

50 (15)

30 (9)

 

 

 

 

 

 

 

 

 

 

 

 

 

25

3000

175 (53)

 

112 (34)

62

(19)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

3600

150 (46)

 

87

(26)

50

(15)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

4200

125 (38)

 

75

(23)

50

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

4800

112 (34)

 

62

(19)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

5400

100 (30)

 

62

(19)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

6000

87 (26)

 

50

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Conductor size is based on maximum 2% voltage drop

Cord Lengths for 240 Volt Loads

YIf unit does not have GFCI receptacles, use GFCI-protected extension cord.

 

 

 

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

 

Current

 

 

 

 

 

 

 

 

 

 

Load (Watts)

4

 

6

 

8

10

12

 

14

(Amperes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

1200

 

 

 

700

(213)

450 (137)

225 (84)

 

200 (61)

 

 

 

 

 

 

 

 

 

 

 

7

1680

 

 

800 (244)

500

(152)

300 (91)

200 (61)

 

125 (38)

 

 

 

 

 

 

 

 

 

 

 

10

2400

800 (244)

 

550 (168)

350

(107)

225 (69)

125 (38)

 

100 (31)

 

 

 

 

 

 

 

 

 

 

15

3600

600 (183)

 

350 (107)

225 (69)

150 (46)

75 (23)

 

60 (18)

 

 

 

 

 

 

 

 

 

 

20

4800

450 (137)

 

275 (84)

175 (53)

100 (31)

60 (18)

 

 

 

 

 

 

 

 

 

 

 

 

25

6000

350 (107)

 

225 (69)

125 (38)

75 (23)

 

 

 

 

 

 

 

 

 

 

 

 

 

30

7000

300 (91)

 

175 (53)

100 (31)

75 (23)

 

 

 

 

 

 

 

 

 

 

 

 

 

35

8400

250 (76)

 

150 (46)

100 (31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

9600

225 (69)

 

125 (38)

75

(23)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

10,800

200 (61)

 

125 (38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

12,000

175 (53)

 

100 (31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Conductor size is based on maximum 2% voltage drop

OM-130 098 Page 43

Image 47
Contents August OM-130Processes Visit our website atFrom Hobart to You Table of Contents Page ARC Rays can burn eyes and skin Symbol UsageArc Welding Hazards Electric Shock can killEngine Hazards Engine Heat can cause fire Battery Explosion can BlindMoving Parts can cause injury Engine Exhaust Gases can killARC Welding can cause interference Principal Safety StandardsEMF Information Radiation can cause interferenceLES Fumé ES ET LES GAZ peuvent ê tre dangereux Signification des symbolesConsignes DE SÉ Curité Lire Avant Utilisation UN Choc É Lectrique peut tuerLE Bruit peut affecter l’ouïe LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux DES PIÈ CES Chaudes peuvent provoquer des brû lures gravesLA Chute DE L’APPAREIL peut blesser DES Organes Mobiles peuvent provoquer des blessures’EXPLOSION DE LA Batterie peut LA Chaleur DU Moteur peut pro- voquer un incendieConsignes relatives aux stimulateurs cardiaques Principales normes de sé curitéInformation sur les champs é lectromagné tiques LE Soudage À L’ARC risque de provoquer des interfé rencesDefinitions Symbols And DefinitionsDimensions, Weights, And Operating Angles SpecificationsWeld, Power, And Engine Specifications 40% Duty Cycle At 400 Amperes Warranty Minutes Welding Minutes RestingFuel Consumption Duty Cycle And OverheatingVolt-Ampere Curves AC Auxiliary PowerOptional AC Power Plant Curves Installing Muffler Pipe InstallationInstalling Welding Generator For 12 Minutes Activating The Dry Charge BatteryDo not overfill battery cells Vent CapsFull Connecting The BatteryEngine Prestart Checks Connect Negative Cable LastPut cap on fitting when cylinder is removed Installing Ether Cylinder Optional Ether Starting AidConnecting To Weld Output Terminals 10 100% Duty Cycle Selecting Weld Cable Sizes100 ft 30 m Or Less OM-130 098 Controls See Section Operating the Welding GeneratorRemote A/V Control Description Of Front Panel Controls See SectionVolt And 240 Volt Duplex Receptacles Operating Auxiliary EquipmentAustralian, British, And South African Receptacle Options Optional Auxiliary Power ReceptaclesGfci Receptacle Option Connecting Optional Auxiliary Power Plant Maintenance and Troubleshooting Maintenance Label Hose Servicing Air CleanerTo clean air filter Stop engineTo replace primary fuel filter Servicing Fuel And Lubrication SystemsTo change oil and filter Models With Automatic Idle Optional Adjusting Engine SpeedStandard Models Full Empty Overload Protection Servicing Optional Ether Starting AidWelding Inspecting And Cleaning Optional Spark ArrestorTroubleshooting Maximum see Section Auxiliary PowerCheck connections to auxiliary power plant see Section EngineCircuit Diagram For Welding Generator Electrical DiagramWetstacking RUN-IN ProcedureFrom flammables Run-In Procedure Using Load BankStop engine Do not touch hot exhaust Bank/gridRun-In Procedure Using Resistance Grid Grounding Generator To Truck Or Trailer Frame Auxiliary Power GuidelinesSelecting Equipment Amperes x Volts = Watts Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Earth ground if supplyingFarm/Home Equipment Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Industrial Motors Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentKVA/HP x HP x Power Required To Start MotorHow Much Power Can Generator Supply? Single-Phase Induction Motor Starting Requirements120 Single-Phase Power Company ServiceObtain and install correct switch Safety practicesCurrent Load Watts Amperes Selecting Extension Cord Use Shortest Cord Possible110 Parts List118 117 116 115 71Includes 113 11465 FIG Dia Part Description Quantity Mkgs 126 102 Optional Equipment Panel, Front w/Components Panel, Front w/Components -1 Item 11 10 GeneratorGenerator -1 Item Includes 114Support ServiceCall Contact your Distributor forHobart Welding Products

3225DX specifications

The Hobart 3225DX is a robust and versatile commercial dishwasher designed to meet the needs of restaurants, catering services, and institutions requiring efficient dishwashing solutions. Engineered for high performance, this machine combines advanced technology with user-friendly features to deliver exceptional cleaning results.

One of the standout features of the Hobart 3225DX is its high capacity. It can wash up to 60 racks per hour, making it suitable for busy kitchens. The machine is designed to handle a wide variety of dishware, glassware, and utensils, ensuring a thorough clean for all types of kitchenware.

Equipped with a powerful two-speed wash pump, the Hobart 3225DX guarantees optimal cleaning efficiency. Users can choose between a standard wash cycle for regular soiled items and a more intense cycle for heavily soiled dishware. This flexibility allows kitchen staff to adjust the machine's performance based on their specific needs.

The dishwasher features an advanced filtration system that minimizes the need for frequent cleaning of the internal components. This system captures food particles and debris, enhancing the machine's longevity and maintaining consistently clean results. Additionally, the Hobart 3225DX is designed with a built-in booster heater that increases water temperature to ensure optimal sanitization, complying with health and safety standards.

User convenience is a key consideration in the design of the Hobart 3225DX. The intuitive controls and clear display make operation straightforward, even for first-time users. The machine is also engineered for easy maintenance, with accessible components that allow for quick service and troubleshooting.

Another notable characteristic is its energy efficiency. The Hobart 3225DX is designed to minimize water and energy consumption without compromising performance. This aligns with the growing emphasis on sustainability in the foodservice industry, offering an eco-friendly solution that helps businesses reduce operational costs.

In summary, the Hobart 3225DX is an efficient, high-capacity commercial dishwasher that combines powerful cleaning capabilities with user-friendly features. Its advanced wash pump, effective filtration system, and energy-efficient design make it an ideal choice for any busy kitchen looking to streamline dishwashing operations and maintain the highest hygiene standards.