12-3. Grounding When Supplying Building Systems

 

 

 

1

Equipment Grounding

 

1

2

 

Terminal

 

2

Grounding Cable

 

GND/PE

 

 

 

Use #10 AWG or larger insulated

 

 

 

 

 

 

copper wire.

 

 

 

3

Ground Device

 

 

 

Y Ground generator to system

 

 

 

 

earth ground if supplying

 

 

 

 

power to a premises (home,

 

 

 

 

shop, farm) wiring system.

 

 

 

Use ground device as stated

 

2

3

 

in electrical codes.

 

 

 

 

ST-800 576-B

12-4. How Much Power Does Equipment Require?

1 Resistive Load

3

2

1

3

VOLTS 115 AMPS 4.5

Hz 60

A light bulb is a resistive load and requires a constant amount of power.

2 Non-Resistive Load

Equipment with a motor is a non-re- sistive load and requires approxi- mately six times more power while starting the motor than when running (see Section 12-8).

3 Rating Data

Rating shows volts and amperes, or watts required to run equipment.

AMPERES x VOLTS = WATTS

EXAMPLE 1: If a drill uses 4.5 amperes at 115 volts, calculate its running power requirement in watts.

4.5 A x 115 V = 520 W

The load applied by the drill is 520 watts.

EXAMPLE 2: If three 200 watt flood lamps are used with the drill from Example 1, add the individual loads to calculate total load.

(200 W + 200 W + 200 W) + 520 W = 1120 W

The total load applied by the three flood lamps and drill is 1120 watts.

S-0623

OM-945 Page 39

Image 43
Contents Description ProcessesFrom Hobart to You Table of Contents Table of Contents Arc Welding Hazards Symbol UsageEngine Hazards Compressed Air Hazards Radiation can cause interference Principal Safety StandardsCalifornia Proposition 65 Warnings EMF InformationLES Fumées ET LES GAZ peuvent être dangereux Signification des symboles− Consignes DE Sécurité − Lire Avant Utilisation UN Choc Électrique peut tuerLE Bruit peut affecter l’ouïe LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux DES Pièces Chaudes peuvent provoquer des brûlures graves’AIR Comprimé peut provoquer des blessures ’EXPLOSION DE LA Batterie peutDES Organes Mobiles peuvent provoquer des blessures LA Chaleur DU Moteur peut pro- voquer un incendieInformation sur les champs électromagnétiques Principales normes de sécurité− Definitions − SpecificationsSymbol Definitions Weld, Power, and Engine SpecificationsGenerator Power Curve Dimensions, Weights, and Operating AnglesDo not move or operate unit where it could tip Duty Cycle Fuel Consumption All ModelsVolt-Ampere Curves Material Thickness Reference ChartInstalling Welding Generator − InstallationOil Engine Prestart Checks Onan-Powered UnitsEngine Prestart Checks Kohler-Powered Units FuelCharger Activating The Dry Charge Battery If ApplicableDo not overfill battery cells Read and follow all instrucConnect negative − cable last Connecting the BatteryInstalling Exhaust Pipe + −Put terminals Connecting to Weld Output TerminalsSelecting Weld Cable Sizes 45 m 60 m 70 m 90 m 105 m 120 mAmperage Selection Table For Stick Smaw Electrodes Front Panel Controls − Operating the Welding GeneratorStandard Receptacles − Operating Auxiliary EquipmentCeptacles, use Wiring Optional 240 Volt Plug Optional Generator Power Receptacles− Maintenance ONAN-POWERED Units Every 500 h Maintenance Label Onan-Powered UnitsEvery 1000 h Stop engine Servicing Air Cleaner Onan-Powered UnitsStop engine and let cool Overload Protection Onan-Powered UnitsServicing Optional Spark Arrestor Onan-Powered Units Stop engine. Disconnect nega- tive − battery cableFull Tools Needed Idle Speed Adjustment Adjusting Engine Speed Onan-Powered UnitsWeld/Power Speed Adjustment Every 20 h Routine Maintenance Kohler-Powered UnitsEvery 25 h Replace unreadable labels Maintenance Label Kohler-Powered Units Servicing Air Cleaner Kohler-Powered Units Servicing Optional Spark Arrestor Kohler-Powered Units Overload Protection Kohler-Powered Units802 339-B / S-0842 Stop engine. Reinstall wrapper Adjusting Engine Speed Kohler-Powered UnitsWelding − TroubleshootingTroubleshooting Generator PowerEngine − Electrical Diagram Selecting Equipment − Generator Power GuidelinesGrounding Generator To Truck Or Trailer Frame Amperes x Volts = Watts Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Earth ground if supplyingFarm/Home Equipment Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Industrial Motors Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentKVA/HP x HP x 1000 = Starting Amperage Power Required To Start MotorHow Much Power Can Generator Supply? Single-Phase Induction Motor Starting RequirementsTypical Connections To Supply Standby Power Current Load Watts Amperes Selecting Extension Cord Use Shortest Cord PossibleWeld current starts when electrode touches work- piece Stick Welding Procedure− Stick Welding Smaw Guidelines Striking an Arc − Scratch Start Technique Electrode and Amperage Selection ChartStriking an Arc − Tapping Technique Good Weld Bead Characteristics Poor Weld Bead CharacteristicsPositioning Electrode Holder Electrode Movement During Welding Conditions That Affect Weld Bead ShapeLap Joint Butt JointsTee Joint Possible Causes Corrective Actions Troubleshooting − PorosityTroubleshooting − Excessive Spatter Weld TestTroubleshooting − Lack Of Penetration Troubleshooting − Incomplete FusionTroubleshooting − Excessive Penetration Troubleshooting − Waviness Of Bead Troubleshooting − Burn-ThroughTroubleshooting − Distortion OM-945 Main Assembly Onan Engine Shown − Parts ListMain Assembly Panel, Front w/Components Panel, Front w/Components -1Item Generator -1Item Support ServiceHobart Welding Products Contact your Distributor for