Allied Air Enterprises 4HP16LT manual 24VAC Power Wiring, Short Cycling

Page 23

60 seconds. The module will continue to display the previous flash code until the condition returns to normal or 24VAC is removed from the module. TRIP and ALERT LEDs flashing at the same time means control circuit voltage is too low for operation.

24VAC Power Wiring

The diagnostic module requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermo- stat. The module cannot be powered by R and C terminals on the defrost board without experiencing nuisance alerts.

 

 

 

Flash Codes (cont.)

 

 

 

 

 

 

LED

Fault Description

Troubleshooting Information

 

 

Status

 

 

 

 

 

 

 

 

 

 

 

ALERT

Short Cycling

1. Thermostat demand signal is intermittent

 

 

(Yellow)

Compressor is

2. Time delay relay or control board defective

 

 

Flash

running

3. If high pressure switch present, go to Flash Code 2 info

 

 

Code 3

only briefly

4. If low pressure switch present, go to Flash Code 1 info

 

 

 

 

 

 

 

 

 

1. Run capacitor has failed

 

 

ALERT

 

2. Low line voltage (contact utility if voltage at disconnect is low)

 

 

(Yellow)

Locked Rotor

* Check wiring connections

 

 

Flash

3. Excessive liquid refrigerant in compressor

 

 

 

 

 

Code 4

 

4. Compressor bearings are seized

 

 

 

 

*Measure compressor oil level

 

 

 

 

 

 

 

 

 

1. Outdoor unit power disconnect is open

 

 

 

 

2. Compressor circuit breaker or fuse(s) is open

 

 

 

 

3. Compressor contactor has failed open

 

 

 

 

* Check compressor contactor wiring and connectors

 

 

ALERT

 

* Check for compressor contactor failure (burned, pitted, or open)

 

 

(Yellow)

Open Circuit

* Check wiring and connectors between supply and compressor

 

 

Flash

* Check for low pilot voltage at compressor contactor coil

 

 

 

 

 

Code 5

 

4. High pressure switch is open and requires manual reset

 

 

 

 

5. Open circuit in compressor supply wiring or connections

 

 

 

 

6. Unusually long compressor protector reset time due to extreme ambient temperature

 

 

 

 

7. Compressor windings are damaged

 

 

 

 

* Check compressor motor winding resistance

 

 

 

 

 

 

 

ALERT

 

1. Run capacitor has failed

 

 

Open Start Circuit

2. Open circuit in compressor start wiring or connections

 

 

(Yellow)

 

 

Current only in run

* Check wiring and connectors between supply and the compressor S terminal

 

 

Flash

 

 

circuit

3. Compressor start winding is damaged

 

 

Code 6

 

 

 

* Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

 

ALERT

Open Run Circuit

1. Open circuit in compressor run wiring or connections

 

 

(Yellow)

* Check wiring and connectors between supply and the compressor R terminal

 

 

Current only in start

 

 

Flash

2. Compressor run winding is damaged

 

 

circuit

 

 

Code 7

* Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

ALERT

Welded Contactor

 

 

 

(Yellow)

1. Compressor contactor has failed closed

 

 

Compressor always

 

 

Flash

2. Thermostat demand signal not connected to module

 

 

runs

 

 

Code 8

 

 

 

 

 

 

 

 

 

 

 

 

ALERT

Low Voltage

1. Control circuit transformer is overloaded

 

 

(Yellow)

 

 

Control circuit less

2. Low line voltage (contact utility if voltage at disconnect is low)

 

 

Flash

 

 

than 17VAC

* Check wiring conditions

 

 

Code 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 11

Page 23

Issue 1004

506468-01

Image 23
Contents 4HP16LT Series Fastener Torque Installation ClearancesTorque Table GeneralRoof Mounting Electrical WiringSlab Mounting Slab MountingWith Auxiliary Heat Thermostat DesignationsWithout Auxiliary Heat Brazing Connection Procedure Outside Unit Placement InstallationInstalling Refrigerant Line Refrigerant Line Sets Transition from Vertical to Horizontal Refrigerant Line Sets Installing Horizontal RunsR22 refrigerant will be used to flush the system Flushing Existing Line Set and Indoor CoilFlushing Connections Manifold Gauge Set Liquid and Suction Line Service ValvesRefrigerant Metering Device To Close Liquid or Suction Line Service Valve Service ValveBall Type Service Valve Valve Open To Open Liquid or Suction Line Service ValveEvacuation Refrigerant Charging Refrigerant Charge AdjustmentAmbient temperature Cooling Cycle Charge Using Weigh-In MethodBlocking Outdoor Coil R410A Temperature/Pressure ChartNormal Operating Pressures Approach Values for TXV Systems Check Charge Using Normal Operating PressuresFilter Drier OperationSensor Temp. / Resistance Range Defrost Board Pressure Switch ConnectionsDelay Mode Issue Defrost Control Board Diagnostic LEDs LED Description System Diagnostic ModuleInterpreting the Diagnostic LEDs Flash CodesShort Cycling 24VAC Power WiringMiswired Module Codes Miswired Module TroubleshootingThermostat Demand Wiring Maintenance Thermostat Operation Case of extended power outageHeat Pump Operation Preservice Check Sequence of Operation Start-Up and Performance ChecklistCooling HeatingSingle Stage Wire Diagram Two Stage Wire Diagram