Allied Air Enterprises 4HP16LT manual Thermostat Designations, Without Auxiliary Heat

Page 4

Thermostat Designations

(Some connections may not apply. Refer to

specific thermostat and indoor unit.)

Without Auxiliary Heat

Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections).

Select line set diameters from Table 2 to ensure that oil returns to the compressor. Size vertical suction riser to maintain minimum velocity at minimum capacity. Recommended line length is 50’ or less. If more than 50’ line set is required, contact Technical Services.

Table 2 shows the diameters for line sets up to 100’ although vertical lift applications and trapping requirements need to be reviewed with Technical Services for line sets over 50’.

Refrigerant Line Set Diameters (in.)

With Auxiliary Heat

B T UH

Liquid Line

Line S et Length and S ize

12 ft. 25 ft. 50 ft. 75 ft. 100 ft.

24,000 3/8 3/8 3/8 3/8 3/8

36,000 3/8 3/8 3/8 3/8 1/2

48,000 3/8 3/8 3/8 1/2 1/2

60,000 3/8 3/8 3/8 1/2 1/2

B T UH

S uction Line

Line S et Length and S ize

Do not connect C (common) connection between indoor unit and thermostat except when required by the indoor thermostat. Refer to thermostat installation instructions. C (common) connection between indoor unit and outdoor unit required for proper operation.

Figure 3

this sesction as well as the section that follows entitled

Flushing Existing Line Set and Indoor Coil.

If this unit is being matched with an approved line set or indoor coil which was previously charged with R-22 refrigerand, the line set and coil must be flushed prior to installation. If the unit is being used with an exisitng indoor coil which was equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 4HP16LT unit.

12 ft. 25 ft. 50 ft. 75 ft. 100 ft. 24,000 3/4 7/8 3/4 7/8 7/8

36,000 7/8 7/8 7/8 7/8 1-1/8

48,000 7/8 7/8 7/8 1-1/8 1-1/8

60,000 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8

For installations exceeding 50’, contact

Technical Services.

Table 2

Page 4

Issue 1004

506468-01

Image 4
Contents 4HP16LT Series Installation Clearances Torque TableGeneral Fastener TorqueElectrical Wiring Slab MountingSlab Mounting Roof MountingWithout Auxiliary Heat Thermostat DesignationsWith Auxiliary Heat Installing Refrigerant Line Outside Unit Placement InstallationBrazing Connection Procedure Refrigerant Line Sets Installing Horizontal Runs Refrigerant Line Sets Transition from Vertical to HorizontalFlushing Existing Line Set and Indoor Coil R22 refrigerant will be used to flush the systemFlushing Connections Refrigerant Metering Device Liquid and Suction Line Service ValvesManifold Gauge Set Service Valve Ball Type Service Valve Valve OpenTo Open Liquid or Suction Line Service Valve To Close Liquid or Suction Line Service ValveEvacuation Ambient temperature Refrigerant Charge AdjustmentRefrigerant Charging Charge Using Weigh-In Method Cooling CycleR410A Temperature/Pressure Chart Blocking Outdoor CoilNormal Operating Pressures Check Charge Using Normal Operating Pressures Approach Values for TXV SystemsOperation Filter DrierDefrost Board Pressure Switch Connections Sensor Temp. / Resistance RangeDelay Mode Issue Defrost Control Board Diagnostic LEDs System Diagnostic Module Interpreting the Diagnostic LEDsFlash Codes LED Description24VAC Power Wiring Short CyclingThermostat Demand Wiring Miswired Module TroubleshootingMiswired Module Codes Maintenance Heat Pump Operation Case of extended power outageThermostat Operation Preservice Check Start-Up and Performance Checklist CoolingHeating Sequence of OperationSingle Stage Wire Diagram Two Stage Wire Diagram