Carrier 50TCQA installation instructions Make Electrical Connections, Field Power Supply

Page 11

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

TO ROOF

DRAIN

BASE RAIL

2˝ (51) MIN

OPEN

VENT

SEE NOTE

ROOF

CURB

DRAIN PLUG

unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 208-v1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected line-side pressure lugs on the

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.

C08022

Fig. 14 - Condensate Drain Piping Details

All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).

Step 10 — Make Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

Field Power Supply —

If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the

power terminal block or at factory-installed option

non-fused disconnect.

 

 

Field power wires are connected to the unit at line-side

50TCQA

pressure lugs on compressor contactor C and indoor fan

 

contactor IFC or terminal board (see wiring diagram label

 

for control box component arrangement) or at

 

factory-installed option non-fused disconnect switch.

 

Max wire size is #2 AWG (copper only). (See Fig. 16)

 

 

 

NOTE: TEST LEADS - Unit may be equipped with

 

short leads (pigtails) on the field line connection points on

 

contactor C or optional disconnect switch. These leads are

 

for factory run-test purposes only; remove and discard

 

before connecting field power wires to unit connection

 

points. Make field power connections directly to line

 

connection pressure lugs only.

 

!WARNING

FIRE HAZARD

Failure to follow this warning could result in intermittent operation or performance satisfaction.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

(See Fig. 15.)

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 15 - Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.

11

Image 11
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Plan for Unit Location Unit Dimensional Drawing 04 07 Size UnitProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit Field Fabricate DuctworkConvert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionDamper Assembly Two Position Damper Hood Removal and Setup Factory OptionEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed Disconnect575 600 Factory-Option Thru-Base ConnectionsSplice BLU + 460 480 H2 + H3Thermostat Field Control WiringHeat Anticipator Settings Units without Thru-Base ConnectionsHeater Model Number Electric HeatersTypical Module Installation PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer controls Outside and Return Air Enthalpy Sensor WiringIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection American A22503 Belden 8772 Columbia 02525 Recommended CablesColor Code Recommendations 2413 orRTU-MP Multi-Protocol Control Board RTU-MP control systemRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs 33ZCT59SPT Economizer controls Space Temperature SPT SensorsFan Status Connecting Discrete Inputs Filter StatusRemote Occupancy Power Exhaust outputCommunication Wiring Protocols General DS = Dip Switch BACnet MS/TP SW3 example shownRTU-MP Troubleshooting Communication LEDs Local AccessLEDs on the RTU-MP show the status of certain functions SystemController LEDsSmoke Detector Locations Controller AssemblyTypical Return Air Detector Location Completing Installation of Return Air Smoke SensorUnit Wire/MOCP Sizing Data 74/80 Pwrd C.O56/59 65/6979/86 74/7944/46 49/5272/78 61/6479/85 55/5843/46 70/7479/84 69/7561/65 75/7984/90 52/5482/90 47/5057/61 70/7688/95 53/5562/66 76/82Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up Install Accessories50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.