Carrier 50TCQA Units without Thru-Base Connections, Field Control Wiring, Thermostat

Page 14

50TCQA

LOW VOLTAGE

CONDUIT

CONNECTOR

HIGH VOLTAGE

CONDUIT

CONNECTOR

C08637

Fig. 20 - Thru-Base Connection Fittings

Field-supplied and field-installed liquidtight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be field cut in the main control box bottom on

control the reversing valve operation. If using an electronic thermostat, configure it for “non-heat pump” operation. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire (35_C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.

Units without Thru-Base Connections —

1.Install power wiring conduit through side panel open- ings. Install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 16.

All Units —

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 10. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use

Typical

Thermostat

Connections

C

G

W2

(Note 2)

W1

O/B/Y2

(Note 1)

Y1

Central

Terminal

Board

X

C

T

GH E

W2

R

M

 

 

 

O

W1

S

 

 

 

T

Y2

A

 

 

T

Y1

 

 

 

the formula shown in the legend for Table 10, Note 2 (see page 44) to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

Field Control Wiring —

The 50TCQA unit requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as factory-installed option or as field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control) or the RTU-MP Controller for Building Management Systems using non-CCN protocols (RTU-MP is available as a factory-installed option only).

Thermostat —

Install a Carrier-approved accessory 2 stage Cooling/Heating thermostat according to installation instructions included with the accessory. The 50TCQ models do not require a thermostat with an O function to

R

R

Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Do not configure for O output.

Note 2: W2 connection not required on units without electric heating.

Field Wiring

C09012

Fig. 21 - Typical Low-Voltage Control Connections

Unit without thru-base connection kit —

Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Central Terminal Board (CTB). See Fig. 22.

NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.

Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available.

14

Image 14
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Unit Dimensional Drawing 04 07 Size Unit Plan for Unit LocationProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Field Fabricate Ductwork Rig and Place UnitEconomizer Hood Removal and Setup Factory Option Ductwork when requiredInstall Outside Air Hood Convert to Horizontal and ConnectTwo Position Damper Hood Removal and Setup Factory Option Damper AssemblyInstall External Condensate Trap and Line Economizer Hood and Two-Position HoodField Power Supply Make Electrical ConnectionsUnits with Factory-Installed Disconnect Convenience Outlets460 480 H2 + H3 Factory-Option Thru-Base ConnectionsSplice BLU + 575 600Units without Thru-Base Connections Field Control WiringHeat Anticipator Settings ThermostatElectric Heaters Heater Model NumberTypical Module Installation PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Space Sensor Mode Thermostat ModeOutside and Return Air Enthalpy Sensor Wiring Economizer controlsIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection 2413 or Recommended CablesColor Code Recommendations American A22503 Belden 8772 Columbia 02525RTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Space Temperature SPT Sensors 33ZCT59SPT Economizer controlsConnecting Discrete Inputs Filter Status Fan StatusDS = Dip Switch BACnet MS/TP SW3 example shown Power Exhaust outputCommunication Wiring Protocols General Remote OccupancyLocal Access RTU-MP Troubleshooting Communication LEDsLEDs SystemController LEDs on the RTU-MP show the status of certain functionsController Assembly Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Typical Return Air Detector LocationUnit Wire/MOCP Sizing Data 65/69 Pwrd C.O56/59 74/8049/52 74/7944/46 79/8655/58 61/6479/85 72/7869/75 70/7479/84 43/4652/54 75/7984/90 61/6570/76 47/5057/61 82/9076/82 53/5562/66 88/95Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Install Accessories Pre-Start and Start-Up50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.