Carrier 50TCQA installation instructions Field Fabricate Ductwork, Rig and Place Unit

Page 7

MAXIMUM ALLOWABLE

DIFFERENCE IN. (MM)

A-B

B-C

A-C

0.5” (13)

1.0” (25)

1.0” (25)

C06110

Fig. 4 - Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.

For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return

should be ducted through the roof deck to comply with applicable fire codes.

For units with accessory electric heaters: Horizontal applications require a minimum clearance to combustible surfaces of 1-in (25 mm) from duct for first 12-in (305 mm) away from unit. Vertical applications do not require a minimum clearance.

Minimum clearance is not required around ductwork.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.

Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

All panels must be in place when rigging. Unit is not designed for handling by fork truck.

Before setting the unit onto the curb, recheck gasketing on curb.

50TCQA

C06005

 

MAX WEIGHT

 

 

DIMENSIONS

 

 

 

 

 

 

 

 

 

UNIT

 

A

 

B

 

C

 

 

 

 

 

 

LB

KG

IN

MM

IN

MM

IN

MM

50TCQA04

755

343

74.38

1889

36.25

921

33.38

848

 

 

 

 

 

 

 

 

 

50TCQA05

760

345

74.38

1889

36.25

921

33.38

848

 

 

 

 

 

 

 

 

 

50TCQA06

840

381

74.38

1889

35.63

905

41.38

1051

 

 

 

 

 

 

 

 

 

50TCQA07

880

399

74.38

1889

37.25

946

41.38

1051

 

 

 

 

 

 

 

 

 

NOTES:

1.Dimensions in ( ) are in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 - Rigging Details

7

Image 7
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Plan for Unit Location Unit Dimensional Drawing 04 07 Size UnitInspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details Rig and Place Unit Field Fabricate DuctworkConvert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionDamper Assembly Two Position Damper Hood Removal and Setup Factory OptionEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed Disconnect575 600 Factory-Option Thru-Base ConnectionsSplice BLU + 460 480 H2 + H3Thermostat Field Control WiringHeat Anticipator Settings Units without Thru-Base ConnectionsHeater Model Number Electric HeatersTypical Module Installation PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer controls Outside and Return Air Enthalpy Sensor WiringIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection American A22503 Belden 8772 Columbia 02525 Recommended CablesColor Code Recommendations 2413 orRTU-MP Multi-Protocol Control Board RTU-MP control systemRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs 33ZCT59SPT Economizer controls Space Temperature SPT SensorsFan Status Connecting Discrete Inputs Filter StatusRemote Occupancy Power Exhaust outputCommunication Wiring Protocols General DS = Dip Switch BACnet MS/TP SW3 example shownRTU-MP Troubleshooting Communication LEDs Local AccessLEDs on the RTU-MP show the status of certain functions SystemController LEDsSmoke Detector Locations Controller AssemblyTypical Return Air Detector Location Completing Installation of Return Air Smoke SensorUnit Wire/MOCP Sizing Data 74/80 Pwrd C.O56/59 65/6979/86 74/7944/46 49/5272/78 61/6479/85 55/5843/46 70/7479/84 69/7561/65 75/7984/90 52/5482/90 47/5057/61 70/7688/95 53/5562/66 76/82EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsSmoke Detectors Pre-Start and Start-Up Install Accessories50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.