Carrier 50TCQA Units with Factory-Installed Disconnect, Convenience Outlets

Page 12

Units with Factory-Installed Disconnect —

The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel. Discard the factory test leads (see Fig. 16).

Units Without Disconnect Option

Convenience Outlets —

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Units with convenience outlet circuits may use

 

 

IFC

 

 

 

(3 Phase

 

C

 

Indoor Motor)

11

13

13

TB

Disconnect

per

NEC

(1 Phase Indoor Motor

and 1 Phase Unit)

multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary.

Two types of convenience outlets are offered on 50TCQA models: Non-powered and unit-powered. Both types

50TCQA

 

L1

L2

L3

 

 

 

 

208/230-1-60

 

 

 

 

208/230-3-60

 

 

 

 

 

460-3-60

 

 

 

 

 

 

575-3-60

 

 

 

 

 

Units With Disconnect Option

 

L1

2

Optional

1

 

Factory

 

 

 

 

 

L2

4

Disconnect

3

 

 

Wiring

 

 

Switch

 

 

 

 

 

 

 

L3

6

 

 

5

 

 

 

 

 

 

Disconnect factory test leads; discard.

C09011

Fig. 16 - Power Wiring Connections

All units -

All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 16 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2 ga AWG per pole.

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.

All field wiring must comply with the NEC and local requirements.

provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 17.

 

Pwd-CO

Convenience

Transformer

Outlet

 

GFCI

 

Pwd-CO

Fuse

Switch

Control Box

Access Panel

C08128

Fig. 17 - Convenience Outlet Location

Installing Weatherproof Cover –

Aweatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet; discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).

12

Image 12
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Unit Dimensional Drawing 04 07 Size Unit Plan for Unit LocationPlan for Sequence of Unit Installation Inspect unitProvide Unit Support Roof Curb Details Field Fabricate Ductwork Rig and Place UnitDuctwork when required Install Outside Air HoodEconomizer Hood Removal and Setup Factory Option Convert to Horizontal and ConnectTwo Position Damper Hood Removal and Setup Factory Option Damper AssemblyInstall External Condensate Trap and Line Economizer Hood and Two-Position HoodField Power Supply Make Electrical ConnectionsUnits with Factory-Installed Disconnect Convenience OutletsFactory-Option Thru-Base Connections Splice BLU +460 480 H2 + H3 575 600Field Control Wiring Heat Anticipator SettingsUnits without Thru-Base Connections ThermostatElectric Heaters Heater Model NumberTypical Module Installation PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Space Sensor Mode Thermostat ModeOutside and Return Air Enthalpy Sensor Wiring Economizer controlsIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables Color Code Recommendations2413 or American A22503 Belden 8772 Columbia 02525RTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Space Temperature SPT Sensors 33ZCT59SPT Economizer controlsConnecting Discrete Inputs Filter Status Fan StatusPower Exhaust output Communication Wiring Protocols GeneralDS = Dip Switch BACnet MS/TP SW3 example shown Remote OccupancyLocal Access RTU-MP Troubleshooting Communication LEDsSystem ControllerLEDs LEDs on the RTU-MP show the status of certain functionsController Assembly Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Typical Return Air Detector LocationUnit Wire/MOCP Sizing Data Pwrd C.O 56/5965/69 74/8074/79 44/4649/52 79/8661/64 79/8555/58 72/7870/74 79/8469/75 43/4675/79 84/9052/54 61/6547/50 57/6170/76 82/9053/55 62/6676/82 88/95Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchSmoke Detectors Install Accessories Pre-Start and Start-Up50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.