Carrier 50TCQA installation instructions RTU-MP Controller Inputs and Outputs

Page 28

50TCQA

Table 8 – RTU-MP Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

Space Temperature Sensor

sptsens

 

AI (10K Thermistor)

J20---1, 2

 

 

 

 

 

Supply Air Temperature

sat

 

AI (10K Thermistor)

J2---1, 2

 

 

 

 

 

Local Outside Air Temperature Sensor

oatsens

 

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

sptopot

 

AI (100K Potentiometer)

J20---3

 

 

 

 

 

Indoor Air Quality

iaq

 

AI (4---20 ma)

J4---2, 3

 

 

 

 

 

Outdoor Air Quality

oaq

 

AI (4---20 ma)

J4---5, 6

Safety Chain Feedback

safety

 

DI (24 VAC)

J1---9

Compressor Safety

compstat

 

DI (24 VAC)

J1---2

 

 

 

 

 

Fire Shutdown

firedown

 

DI (24 VAC)

J1---10

 

 

 

 

 

Enthalpy Switch

enthalpy

 

DI (24 VAC)

J2---6, 7

Humidistat Input Status

humstat

 

DI (24 VAC)

J5---7, 8

 

 

 

CONFIGURABLE

INPUTS*

 

Space Relative Humidity

sprh

 

AI (4---20 ma)

J4---2,3 or J4---5,6

 

 

 

 

 

 

Outside Air Relative Humidity

oarh

 

AI (4---20 ma)

 

 

 

 

 

 

 

Supply Fan Status

fanstat

 

DI (24 VAC)

J5---1,2 or J5---3,4 or

 

 

 

 

 

 

Filter Status

filtstat

 

DI (24 VAC)

 

J5 5,6 or J5---7,8

 

 

 

 

 

 

Remote Occupancy Input

remocc

 

DI (24 VAC)

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUTS

 

 

 

Economizer Commanded Position

econocmd

 

4---20ma

J2---5

 

 

 

 

 

Supply Fan Relay State

sf

 

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1---7

 

 

 

 

 

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1---6

 

 

 

 

 

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

aux_2

 

DO Relay (24VAC , 1A)

J11---3

 

 

 

 

 

Dehumidification Relay State

humizer

 

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field--- installation.

The RTU-MP controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor - On FIOP-equipped 50TCQ unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 29.

Outdoor Air Temperature (OAT) Sensor - The OAT is factory-mounted in the EconoMi$er2 (FIOP or

accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

EconoMi$er2 - The RTU-MP control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU-MP control; EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Field Connections - Field connections for accessory sensors and input devices are made the RTU-MP, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU-MP must be routed through the raceway built into the corner post as shown in Fig. 22.

28

Image 28
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Unit Dimensional Drawing 04 07 Size Unit Plan for Unit LocationInspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details Field Fabricate Ductwork Rig and Place UnitDuctwork when required Install Outside Air HoodEconomizer Hood Removal and Setup Factory Option Convert to Horizontal and ConnectTwo Position Damper Hood Removal and Setup Factory Option Damper AssemblyInstall External Condensate Trap and Line Economizer Hood and Two-Position HoodField Power Supply Make Electrical ConnectionsUnits with Factory-Installed Disconnect Convenience OutletsFactory-Option Thru-Base Connections Splice BLU +460 480 H2 + H3 575 600Field Control Wiring Heat Anticipator SettingsUnits without Thru-Base Connections ThermostatElectric Heaters Heater Model NumberTypical Module Installation PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Space Sensor Mode Thermostat ModeOutside and Return Air Enthalpy Sensor Wiring Economizer controlsIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables Color Code Recommendations2413 or American A22503 Belden 8772 Columbia 02525RTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Space Temperature SPT Sensors 33ZCT59SPT Economizer controlsConnecting Discrete Inputs Filter Status Fan StatusPower Exhaust output Communication Wiring Protocols GeneralDS = Dip Switch BACnet MS/TP SW3 example shown Remote OccupancyLocal Access RTU-MP Troubleshooting Communication LEDsSystem ControllerLEDs LEDs on the RTU-MP show the status of certain functionsController Assembly Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Typical Return Air Detector LocationUnit Wire/MOCP Sizing Data Pwrd C.O 56/5965/69 74/8074/79 44/4649/52 79/8661/64 79/8555/58 72/7870/74 79/8469/75 43/4675/79 84/9052/54 61/6547/50 57/6170/76 82/9053/55 62/6676/82 88/95EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsSmoke Detectors Install Accessories Pre-Start and Start-Up50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.