Carrier 50TCQA installation instructions Indoor CO2 Sensor 33ZCSENCO2 Connections

Page 23

H G 24 VAC OR

+ - 24 VDC

+ 0-10VDC

- SIG COM + 4-20mA

NC }ALARM

COM RELAY

NO CONTACTS

2 1 8 7 6 5 4 3 2 1

J3 J4

C08635

Refer to Form 33CS-58SI, PremierLink Installation, Start-up, and Configuration Instructions, for detailed configuration information

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 40. The outdoor air CO2 sensor must be located in the economizer outside air hood.

50TCQA

Fig. 38 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 38. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-11. See Fig. 39.

IAQ Sensor

TB1PL SEN 9 J5-5

TB1

COM 11 J5-3

24 VAC

C08636

Fig. 39 - Indoor CO2 Sensor (33ZCSENCO2)

Connections

COVER REMOVED

SIDE VIEW

C07135

Fig. 40 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor — A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 38. Connect the 4 to 20 mA terminal to the TB1-13 terminal of the 50TCQ. Connect the SIG COM terminal to the TB1-11 terminal of the 50TCQA. See Fig. 41.

OAQ Sensor/RH Sensor

TB1PL SEN 13 J5-2

TB1

COM 11 J5-3

24 VAC

C08275

Fig. 41 - Outdoor CO2 Sensor Connections

Smoke Detector/Fire Shutdown (FSD) — This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory-wired for PremierLink FSD operation when PremierLink is factory-installed.

23

Image 23
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Plan for Unit Location Unit Dimensional Drawing 04 07 Size UnitProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit Field Fabricate DuctworkConvert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionDamper Assembly Two Position Damper Hood Removal and Setup Factory OptionEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed Disconnect575 600 Factory-Option Thru-Base ConnectionsSplice BLU + 460 480 H2 + H3Thermostat Field Control WiringHeat Anticipator Settings Units without Thru-Base ConnectionsHeater Model Number Electric HeatersTypical Module Installation PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer controls Outside and Return Air Enthalpy Sensor WiringIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection American A22503 Belden 8772 Columbia 02525 Recommended CablesColor Code Recommendations 2413 orRTU-MP Multi-Protocol Control Board RTU-MP control systemRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs 33ZCT59SPT Economizer controls Space Temperature SPT SensorsFan Status Connecting Discrete Inputs Filter StatusRemote Occupancy Power Exhaust outputCommunication Wiring Protocols General DS = Dip Switch BACnet MS/TP SW3 example shownRTU-MP Troubleshooting Communication LEDs Local AccessLEDs on the RTU-MP show the status of certain functions SystemController LEDsSmoke Detector Locations Controller AssemblyTypical Return Air Detector Location Completing Installation of Return Air Smoke SensorUnit Wire/MOCP Sizing Data 74/80 Pwrd C.O56/59 65/6979/86 74/7944/46 49/5272/78 61/6479/85 55/5843/46 70/7479/84 69/7561/65 75/7984/90 52/5482/90 47/5057/61 70/7688/95 53/5562/66 76/82Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up Install Accessories50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.