Carrier 50TCQA Recommended Cables, Color Code Recommendations, 2413 or, Red Ground White Black

Page 25

At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.

NOTE: Carrier device default is 9600 band.

COMMUNICATION BUS WIRE SPECIFICATIONS — The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded 3-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.

See Table 6 for recommended cable.

Table 6 – Recommended Cables

MANUFACTURER

CABLE PART NO.

 

 

Alpha

2413 or 5463

 

 

American

A22503

 

 

Belden

8772

 

 

Columbia

02525

 

 

NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -20_C to 60_C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.

The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).

Connecting CCN bus:

NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See Table 7 for the recommended color code.

Table 7 – Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

CCN PLUG PIN

COLOR

NUMBER

 

 

 

 

+

Red

1

 

 

 

Ground

White

2

 

 

 

---

Black

3

 

 

 

Connect the CCN (+) lead (typically RED) to the unit’s TB1-12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB1-14 terminal. Connect the CCN (-) lead (typically BLK) to the unit’s TB1-16 terminal. See Fig. 46.

CCN Bus

 

 

 

 

TB1

PL

+ (RED)

12

 

J2-1

 

TB1

GND (WHT) 14 J2-2

TB1

– (BLK) 16 J2-3

C08276

Fig. 46 - PremierLink CCN Bus Connections

50TCQA

25

Image 25
Contents Installation Instructions 50TCQA Unit Dimensional Drawing 04 07 Size Units Plan for Unit Location Unit Dimensional Drawing 04 07 Size UnitInspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details Rig and Place Unit Field Fabricate DuctworkInstall Outside Air Hood Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Convert to Horizontal and ConnectDamper Assembly Two Position Damper Hood Removal and Setup Factory OptionEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed DisconnectSplice BLU + Factory-Option Thru-Base Connections460 480 H2 + H3 575 600Heat Anticipator Settings Field Control WiringUnits without Thru-Base Connections ThermostatHeater Model Number Electric HeatersTypical Module Installation PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer controls Outside and Return Air Enthalpy Sensor WiringIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Color Code Recommendations Recommended Cables2413 or American A22503 Belden 8772 Columbia 02525RTU-MP Multi-Protocol Control Board RTU-MP control systemRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs 33ZCT59SPT Economizer controls Space Temperature SPT SensorsFan Status Connecting Discrete Inputs Filter StatusCommunication Wiring Protocols General Power Exhaust outputDS = Dip Switch BACnet MS/TP SW3 example shown Remote OccupancyRTU-MP Troubleshooting Communication LEDs Local AccessController SystemLEDs LEDs on the RTU-MP show the status of certain functionsSmoke Detector Locations Controller AssemblyTypical Return Air Detector Location Completing Installation of Return Air Smoke SensorUnit Wire/MOCP Sizing Data 56/59 Pwrd C.O65/69 74/8044/46 74/7949/52 79/8679/85 61/6455/58 72/7879/84 70/7469/75 43/4684/90 75/7952/54 61/6557/61 47/5070/76 82/9062/66 53/5576/82 88/95EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsSmoke Detectors Pre-Start and Start-Up Install Accessories50TCQA 50TCQA Catalog No 50TCQ---01SI

50TCQA specifications

The Carrier 50TCQA is a split system air conditioner known for its efficiency, reliability, and innovative technology. Designed for commercial and residential applications, this model provides a solution that combines comfort with cost-effectiveness, making it a popular choice for homeowners and businesses alike.

One of the key features of the Carrier 50TCQA is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures optimal energy efficiency. This means that users can enjoy lower utility bills while maintaining a comfortable indoor climate. The unit is engineered to perform well even in extreme temperatures, providing effective cooling and heating when needed.

This model employs a scroll compressor, which is known for its durability and quiet operation. The compressor's design allows for smoother operation and reduced noise levels, making it suitable for use in noise-sensitive environments. Additionally, the 50TCQA is equipped with a multi-speed fan, allowing for adjustable airflow to match the specific comfort requirements of different spaces.

The Carrier 50TCQA utilizes advanced refrigerant technology, specifically the environmentally friendly R-410A refrigerant. This refrigerant helps to reduce greenhouse gas emissions and provides efficient cooling without depleting the ozone layer. The unit's design is also focused on minimizing refrigerant leaks, ensuring environmental safety and reliability over the long term.

Ease of installation and maintenance is another significant characteristic of the Carrier 50TCQA. The unit features a compact and lightweight design, making it easier for technicians to install and service. Moreover, the system is equipped with diagnostic capabilities that allow for quick identification of issues, enhancing service efficiency and reducing downtime.

In terms of control, the Carrier 50TCQA offers a sophisticated thermostat option that includes programmable settings. Users can easily set desired temperatures, timers, and operating modes, ensuring optimal comfort throughout the day and night.

Overall, the Carrier 50TCQA presents a robust solution for climate control needs. With its energy-efficient performance, advanced technologies, and user-friendly features, it embodies Carrier's commitment to providing high-quality heating and cooling solutions that cater to modern lifestyle requirements. This model stands out as an excellent option for those looking to invest in a reliable HVAC system that enhances comfort while being mindful of energy consumption and environmental considerations.