Commissioning

ACT 250 remote connector characteristics

Voltage control mode

When units containing the control circuits are equipped with dry contact outputs, it is the customer's responsibility to use the outputs in

compliance with safety regulations.

 

6

 

 

The inputs are activated when

 

1

11

+

an AC or DC voltage is

 

 

12

 

 

+

applied. The voltage should be

 

 

13

 

 

+

between 15 and 24 Volts.

 

 

 

 

 

14

+

(15-pin Sub-D female

 

10

15

 

5

connector).

 

 

 

+15 V

 

 

Cable supplied

 

0 V

 

by customer

 

January 2001

Principle of voltage- controlled optocoupled inputs

Example : Ext. safety activated

 

6

1

11

 

12

 

13

 

14

 

10

5

15

 

O V

Ext. safety

11

Select Mode

12

Inactive = the external safety device is activated (e.g. an emergency stop)

Active = pump operation authorised

Select “status” or “pulse” command mode. This affects the START/STOP and STANDBY commands.

12 - inactive = “status” mode

 

Start

 

 

 

 

Start

Stop

 

 

 

Stop

 

 

 

 

Ex. pin 14

nominal

standby

 

 

nominal

 

standby

 

 

 

 

 

 

 

speed

 

 

 

speed

 

 

Ex. pin 13

12 - active = “pulse” mode

Stop

 

 

Start

 

 

Stop

 

 

Start

 

Ex. pin 14

nominal

 

 

standby

 

nominal

 

standby

 

 

 

 

 

 

speed

 

 

 

speed

 

Ex. pin 13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+15 V

External contact supplied by customer

Standby Mode Inactive = operation at nominal speed

13Active = operation at reduced speed

Start/Stop

Inactive = Stop

14Active = Start

15Common for inputs

Alcatel Vacuum Technology France - ACT 250 addendum

11

Image 12 Contents
ACT Contents Syntax conventions applicable to all commands UsePresentation ACT 250 controllerAccessories 108935Europe 108936 108948 Local control mode Remote controlThere are three possible remote control modes ACT 250 box controller control modesACT 250 OEM controller control modes ACT 250 controller technical characteristics ACT 250 box dimensions in mmACT 250 OEM dimensions in mm Safety instructions CommissioningACT 250 controller electrical connections ACT 250 remote connector characteristics Voltage control modeExt. safety Select Mode Principle of voltage- controlled optocoupled inputsSignalling on output contacts ACT 250 remote connector wiring Use in remote control modeWiring the RS 232 or RS 485 serial link RS 232 / 485 serial linkParity Baud rate 9600 4800Detailed description of RS commands Syntax conventions applicable to all commandsResult #aaa,ok or Err2 #adrCKSOFFCRLF Result #adr,ok,S For CksonEnables DataLogger operation RS232 only Result #adr,ok or Err2IDN #adrECHOFFCRLFIdentifies the device which is communicating, and its Software versionLEV LNGNSP Syntax ResultOPT RPMSAV Syntax Result See also SELResult #adr,ok or #adr,ErrX If error SELDefines the character which separates the parameters A reply Syntax #adrSEPnnnCRLFSET SHTSPD Syntax Result See also LEVTMP Defines the turbomolecular pump operating stateUse Controlling the pump from the ACT 250 controllerStarting the pump with the Start switch Precautions Local mode operation Controller functionsIndication of rotation during operation controller on Use France GermanyItaly Japan