Carrier 50HQP072-120 specifications DIP Switch Block S2 Accessory 1 Relay Options, Oad

Page 21

AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.

LOW PRESSURE SETTING — The Deluxe D Control can be configured for Low Pressure Setting (LP). Select jumper 1 (JW1-LP Norm Open) for choosing between low pressure in- put normally opened or closed. To configure for normally closed operation, do not clip the jumper. To configure for nor- mally open operation, clip the jumper.

Deluxe D Control DIP Switches — The Deluxe D Control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 13.

DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D Control configuration: Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

Compressor Relay Staging Operation — Switch 2 will enable or disable compressor relay staging operation. The compressor relay can be set to turn on with stage 1 or stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave ap- plications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to stage 2, the compressor will have a 3-second delay before ener- gizing during stage 2 demand.

NOTE: If DIP switch is set for stage 2, the alarm relay will not cycle during Test mode.

Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.

O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.

Dehumidification Fan Mode — Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu- midification mode. The fan speed relay will remain OFF dur- ing cooling stage 2. Select ON for normal mode. The fan speed relay will turn on during cooling stage 2 in normal mode.

Switch 6 — Not used.

Boilerless Operation — Switch 7 provides selection of boil- erless operation and works in conjunction with switch 8. In boilerless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover tempera- ture set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.

Boilerless Changeover Temperature — Switch 8 on S1 pro- vides selection of boilerless changeover temperature set point. Select OFF for set point of 10.0 C or select ON for set point of 4.4 C.

If switch 8 is set for 10.0 C, then the compressor will be used for heating as long as the FP1 is above 10.0 C. The

compressor will not be used for heating when the FP1 is below

10.0C and the compressor will operate in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 termi- nals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.

DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is used to configure accessory relay options. See Fig. 13.

Switches 1 to 3 — These DIP switches provide selection of Accessory 1 relay options. See Table 8 for DIP switch combinations.

Switches 4 to 6 — These DIP switches provide selection of Accessory 2 relay options. See Table 9 for DIP switch combinations.

Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification fan mode the fan speed relay will remain off during cooling stage 2 if terminal H is active. In high fan mode, the fan enable and fan speed relays will turn on when terminal H is active. Set the switch to ON for auto dehumidification fan mode or to OFF for high fan mode.

Switch 8 — Not used.

Table 8 — DIP Switch Block S2 —

Accessory 1 Relay Options

ACCESSORY 1

DIP SWITCH POSITION

RELAY OPTIONS

1

2

3

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

LEGEND

 

 

 

NSB — Night Setback

OAD — Outside Air Damper

NOTE: All other DIP switch combinations are invalid.

Table 9 — DIP Switch Block S2 —

Accessory 2 Relay Options

ACCESSORY 2

DIP SWITCH POSITION

RELAY OPTIONS

4

5

6

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

LEGEND

 

 

 

NSB — Night Setback

OAD — Outside Air Damper

NOTE: All other switch combinations are invalid.

Deluxe D Control Accessory Relay Configura- tions — The following accessory relay settings are applica- ble for both Deluxe D controls only:

CYCLE WITH FAN — In this configuration, the relay will be ON any time the Fan Enable relay is on.

CYCLE WITH COMPRESSOR — In this configuration, the relay will be ON any time the Compressor relay is on.

DIGITAL NIGHT SET BACK (NSB) — In this configura- tion, the relay will be ON if the NSB input is connected to ground C.

NOTE: If there are no relays configured for digital NSB, then the NSB and override (OVR) inputs are automatically config- ured for mechanical operation.

21

Image 21
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50HQP072-120 Units Unit Dimensions Typical Horizontal Installation Hanger Brackets Install Condensate Piping DrainRemoving Panels Supply/Return Hose Kit Install Field Power Supply WiringTypical Ground-Water Piping Installation Material Water Quality GuidelinesFP1 DPPFP2 HpwrSee legend and notes on LWT SATSPT Electrical Data 50HQP072-120 Dual Point Power Units Electrical Data 50HQP072-120 Standard UnitsLow Voltage VA Ratings Jumper Locations Install Field Control WiringPRE-START-UP Airflow Blower Data 50HQP072Blower Data 50HQP096 Blower Data 50HQP120 Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsAccessory DIP Switch Position Relay Options OADSTART-UP Unit Start-Up in Cooling ModeOperating Limits Start Up SystemUnit Start-Up in Heating Mode Coaxial Water Pressure DropSize Antifreeze Percentages by Volume Approximate Fluid Volume L Per 30 M of PipeOperation Units with Aquazone Complete C ControlAquazone Deluxe D Control LED Indica System TestService Fault DescriptionsComplete C Control LED Code Gravity Flow Method a50-8586 Air Coil Fan Motor Removal Refrigerant ChargingUnit Size Component Drive Package 50HQP Sheave AlignmentThermistor Nominal Resistance TroubleshootingFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Page Copyright 2010 Carrier Corporation II. START-UP START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis