TROUBLESHOOTING

When troubleshooting problems with a WSHP, see Table 18.

Thermistor — A thermistor may be required for single- phase units where starting the unit is a problem due to low voltage. See Fig. 26 for thermistor nominal resistance.

Control Sensors — The control system employs 2 nom- inal 10,000 ohm thermistors (FP1 and FP2) that are used for freeze protection. Be sure FP1 is located in the discharge fluid and FP2 is located in the air discharge. See Fig. 27.

Resistance (kOhm)

90.0

80.0

70.0

60.0

50.0

40.0

30.0

20.0

10.0

0.0

-17.7 -6.6 4.4 15.6 26.7 37.8 48.9 60.0

Temperature (C)

Fig. 26 — Thermistor Nominal Resistance

AIRFLOW

(°C)

THERMISTOR

AIR

COIL

AIRFLOW

(°C)

EXPANSION

VALVE

FP2FP1

COAX

SUCTION

COMPRESSOR

DISCHARGE

CONDENSATE

 

 

 

 

 

 

 

 

 

 

OVERFLOW

LIQUID

 

 

 

 

(CO)

 

 

 

 

LINE

WATER IN

WATER OUT

 

AIR COIL

 

WATER

 

 

 

 

FREEZE

 

 

 

 

PROTECTION

COIL

 

 

 

 

 

PROTECTION

 

 

LEGEND

COAX — Coaxial Heat Exchanger

Airflow

Refrigerant Liquid Line Flow

a50-8163

Fig. 27 — FP1 and FP2 Thermistor Location

30

Image 30
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50HQP072-120 Units Unit Dimensions Typical Horizontal Installation Install Condensate Piping Drain Hanger BracketsRemoving Panels Install Field Power Supply Wiring Supply/Return Hose KitTypical Ground-Water Piping Installation Water Quality Guidelines MaterialFP2 DPPFP1 HpwrSee legend and notes on LWT SATSPT Electrical Data 50HQP072-120 Dual Point Power Units Electrical Data 50HQP072-120 Standard UnitsLow Voltage VA Ratings Install Field Control Wiring Jumper LocationsPRE-START-UP Blower Data 50HQP072 AirflowBlower Data 50HQP096 Blower Data 50HQP120 Complete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigField Selectable Inputs Accessory DIP Switch Position Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options OADOperating Limits Unit Start-Up in Cooling ModeSTART-UP Start Up SystemUnit Start-Up in Heating Mode Coaxial Water Pressure DropSize Operation Approximate Fluid Volume L Per 30 M of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlSystem Test Aquazone Deluxe D Control LED IndicaService Fault DescriptionsComplete C Control LED Code Gravity Flow Method a50-8586 Refrigerant Charging Air Coil Fan Motor RemovalSheave Alignment Unit Size Component Drive Package 50HQPTroubleshooting Thermistor Nominal ResistanceTroubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Page Copyright 2010 Carrier Corporation START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis