Carrier 50HQP072-120 specifications Unit Does Not Operate

Page 32

Table 18 — Troubleshooting (cont)

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

 

 

 

 

 

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

Check fan power enable relay operation (if present).

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in

 

 

X

Reversing valve

Set for cooling demand and check 24-vac on RV coil and at control.

Cooling

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

operating engage and disengage RV coil voltage to push valve.

 

 

 

 

X

Thermostat setup

Check for ‘O’ RV setup not ‘B’.

 

 

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil.

Insufficient Capacity/

 

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

X

X

Leaky ductwork

Check supply and return-air temperatures at the unit and at distant

 

 

 

 

 

 

duct registers if significantly different, duct leaks are present.

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling.

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

 

 

 

 

X

Defective reversing valve

Perform RV touch test.

 

 

 

X

X

Thermostat improperly

Check location and for air drafts behind thermostat.

 

 

 

 

 

located

 

 

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

 

 

X

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

heating

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

 

 

X

 

Air temperature out of range

Bring return-air temperature within design parameters.

 

 

 

 

 

in heating

 

 

 

 

 

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

 

 

 

X

X

Non-condensables in

Vacuum system and reweigh in charge.

 

 

 

 

 

system

 

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

Low Suction Pressure

 

X

 

Reduced water flow in

Check pump operation or water valve operation/setting.

 

 

 

 

 

heating

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

 

 

range

 

 

 

 

 

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

 

 

parameters.

 

 

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air

 

X

 

Too high airflow

Check blower.

Temperature in Heating

 

X

 

Poor performance

See ‘Insufficient Capacity’ above.

High Humidity

 

 

X

Too high airflow

Check blower.

 

 

 

 

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

LEGEND

 

 

 

 

FP

Freeze Protection

 

 

 

 

HP

High Pressure

 

 

 

 

LED — Light-Emitting Diode

 

 

 

 

LP

Low Pressure

 

 

 

 

RV

Reversing Valve

 

 

 

 

32

Image 32
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50HQP072-120 Units Unit Dimensions Typical Horizontal Installation Install Condensate Piping Drain Hanger BracketsRemoving Panels Install Field Power Supply Wiring Supply/Return Hose KitTypical Ground-Water Piping Installation Water Quality Guidelines MaterialDPP FP1FP2 HpwrSee legend and notes on SPT LWTSAT Low Voltage VA Ratings Electrical Data 50HQP072-120 Dual Point Power UnitsElectrical Data 50HQP072-120 Standard Units Install Field Control Wiring Jumper LocationsPRE-START-UP Blower Data 50HQP072 AirflowBlower Data 50HQP096 Blower Data 50HQP120 Field Selectable Inputs Complete C Control Jumper Settings See FigDeluxe D Control Jumper Settings See Fig DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsAccessory DIP Switch Position Relay Options OADUnit Start-Up in Cooling Mode START-UPOperating Limits Start Up SystemSize Unit Start-Up in Heating ModeCoaxial Water Pressure Drop Approximate Fluid Volume L Per 30 M of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlSystem Test Aquazone Deluxe D Control LED IndicaComplete C Control LED Code ServiceFault Descriptions Gravity Flow Method a50-8586 Refrigerant Charging Air Coil Fan Motor RemovalSheave Alignment Unit Size Component Drive Package 50HQPTroubleshooting Thermistor Nominal ResistanceTroubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Page Copyright 2010 Carrier Corporation START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis