Sanyo CVW-EXA124, CVW-EXA284 Joining Instructions,  Perimeter gasket is required by NSF

Page 11

3.7Joining Instructions

3.7.1Applying gasket (for connecting cases or installing side panels).

Make sure that all SANYO Cases are resting level.

Make sure that all required parts for joining are present (gasket, bolts, joint covers, nuts, etc.).

Remove all Rear Interior Panels, Wire Racks, Deck Pans, and Front Air Grilles from the far right and left ends of each case being joined.

Thoroughly clean all surfaces where the gasket will be placed to remove anything that might affect adhesion.

Place gasket along the areas shown in bold in the drawing at bottom. When connecting two cases, apply gasket to one case only.

CAUTION!

Perimeter gasket is required by NSF.

Do not stretch or twist gasket when applying.

Do not leave gaps. Always overlap gasket rather than leaving gaps.

Gasket ends that are open must be sealed off by applying silicone at the installation site.

Insufficient or improper sealing may lead to insufficient cooling and condensation.

Gasket

Important for

Preventing Condensation

11

Image 11
Contents 80 7/8, L 96 3/8 / H 80 7/8, L 144 5/8 MULTI-DECK Fresh Produce CasesActivity Safety Precautions Table of Contents Care and Cleaning Guidelines CVW-EXA284 CVW-EXA224 SpecificationsCVW-EXA184 CVW-EXA124 External Dimensions Footprint DimensionsCVW-EXA184 / CVW-EXA124 Location Unloading and Carpentry ProceduresUnloading Instructions & Precautions NSF CertificationCase Leveling Aligning Cases Perimeter gasket is required by NSF Joining InstructionsConnecting cases CVW-EXA184/124 Installing Patch EndsCVW-EXA284/224 Installing Kickplate Installing Handrail and Bumper Piping Plumbing, Refrigeration Refrigeration, Plumbing & Electrical ProceduresElectrical Data Electrical Guidelines & PrecautionsWiring Wiring Color CodeWiring Diagram Load Limits OperationMagnet Installing FDA/NSF ThermometerMirrors, Fluorescent Lamps, Drain Trap Monthly Cleaning Care and Cleaning GuidelinesExterior Panels Daily Cleaning Honeycomb Assemblies at least every 3 months To replace the fan motors ServiceReplacing Fan Motors and Blades For models with Standard-type AC Fan Motors For models with high-efficiency-type DC fan motors To replace electronic ballasts Replacing Electronic BallastsLamp Cover END CAP Replacing Fluorescent LampsSporlan Expansion Valve DanfossPage Sanyo E & E Corporation