Carrier 50PCH Field-Supplied Sensors for Wshp Open Controller, SPT Sensors, A50-8443, Rnet Wiring

Page 21

WSHP OPEN WIRING — The WSHP Open controller will be factory wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open controller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.

WARNING

Disconnect all power to the unit before performing mainte- nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.

Wiring Sensors to Inputs — Sensors can be wired to the WSHP Open controller’s inputs. See Table 4.

All field control wiring that connects to the WSHP Open con- troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.

1.Pass control wires through the hole provided in the corner post.

2.Feed the wires through the raceway to the WSHP Open controller.

3.Connect the wires to the removable Phoenix connectors.

4.Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con- troller is configurable with the following field-supplied sen- sors. See Table 4.

Table 4 — Field-Supplied Sensors for

WSHP Open Controller

SENSOR

NOTES

Space Temperature Sensor

Field Installed (Must be used with

(SPT)

WSHP Open controller.)

Outdoor Air

Network Sensor

Temperature Sensor

 

Indoor Air Quality Sensor

Required only for demand

(Separate Sensor)

control ventilation.

Space Relative Humidity

Separate Sensor

Sensor

 

NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.

For specific details about sensors, refer to the literature sup- plied with the sensor.

Wiring a SPT Sensor — A WSHP Open controller is connect- ed to a wall-mounted space temperature (SPT) sensor to moni- tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors. See Table 5.

Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combina- tions of devices wired in a daisy-chain configuration:

1 SPT Plus, SPT Pro, or SPT Pro Plus sensors

1 to 4 SPT Standard sensors

1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

Any of the above combinations, plus up to 2 BACview6 Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.

Use the specified type of wire and cable for maximum signal integrity. See Table 6.

Table 5 — SPT Sensors

SENSOR

PART

FEATURES

NUMBER

SPT

SPS

• Local access port

Standard

• No operator control

 

 

 

• Slide potentiometer to adjust set point

SPT Plus

SPPL

• Manual on button to override schedule

• LED to show occupied status

 

 

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

 

 

• Warmer and cooler buttons to adjust set

SPT Pro

SPP

point

• Info button to cycle through zone and

 

 

 

 

outside air temperatures, set points, and

 

 

local override time

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

 

 

• Warmer and cooler buttons to adjust set

SPT Pro

 

point

SPPF

• Info button to cycle through zone and

Plus

 

outside air temperatures, set points, and

 

 

 

 

local override time

 

 

• Local access port

 

 

• Fan speed*

*The SPT Pro Plus fan speed adjustment has no effect in this application.

Table 6 — Rnet Wiring Specifications

RNET WIRING SPECIFICATIONS

Description

4 conductor, unshielded, CMP,

plenum rated cable

 

Conductor

18 AWG

Maximum Length

500 ft

Recommended Coloring

Jacket: white

Wiring: black, white, green, red

 

UL Temperature

32 to 167 F

Voltage

300-vac, power limited

Listing

UL: NEC CL2P, or better

LEGEND

 

AWG — American Wire Gage

CMP — Communications Plenum Cable

NEC — National Electrical Code

UL — Underwriters Laboratories

To wire the SPT sensor to the controller:

1.Partially cut, then bend and pull off the outer jacket of the Rnet cable(s), being careful not to nick inner insulation.

2.Strip about 1/4 in. of the inner insulation from each wire. See Fig. 27.

OUTER JACKET

a50-8443

.25 IN.

INNER INSULATION

Fig. 27 — Rnet Cable Wire

3.Wire each terminal on the sensor to the same terminal on the controller. See Fig. 18-20. Table 7 shows the recom- mended Rnet wiring scheme.

Table 7 — Rnet Wiring

WIRE

TERMINAL

Red

+12-v

Black

.Rnet

White

Rnet+

Green

Gnd

NOTE: The wire should be connected to the terminal shown.

21

Image 21
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PCH,PCV Units A50-8695 SizeIPT Electric Heat A50-7842efA50-8696 Back Discharge Side DischargeMount the Unit Install Condensate DrainA50-8489 A50-6260efA50-6262ef A50-6261tfMetal Hose Minimum Bend Radii Copper FPT/PVCFitting Wire Field Power SupplyA50-8490 A50-8491 Sensor, Low Temperature Protection Air CoilRVS Reversing Valve SolenoidHpws A50-8492LON A50-8493A50-8440 National Electrical Code Optional Wiring Temperature Switch8697 A50Units with Deluxe D and Wshp Open Multiple Protocol Controls 8698Wshp Open Control A50-8162 50PCH,PCV Unit Electrical DataWire Field Controls A50-8441A50-8442 Rnet Wiring Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller SPT SensorsPRE-START-UP 50PCH,PCV Blower Performance High-Static Unit 50PCH,PCV Blower Performance Standard UnitFAN Rated MIN PCV Speed Airflow CFMComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits 50PCH,PCV Units Cooling Heating Water Flow Rate GPM50PC009 Typical Unit Operating Pressures and Temperatures 50PC006 Typical Unit Operating Pressures and Temperatures50PC012 Typical Unit Operating Pressures and Temperatures Entering Cooling Heating Water50PC018 Typical Unit Operating Pressures and Temperatures 50PC015 Typical Unit Operating Pressures and Temperatures50PC024 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat50PC036 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC042 Typical Unit Operating Pressures and Temperatures Water Air Temp50PC048 Typical Unit Operating Pressures and Temperatures Unit Start-Up Heating Mode50PC060 Typical Unit Operating Pressures and Temperatures Unit Start-Up with Wshp Open ControlsBACview6 Display Interface A50-8444Coaxial Water Pressure Drop Pressure DROP, psi kPaGpm 30 F 50 F 70 F 90 F 10 C 21 C 32 C 006 009 Units with Aquazone Complete C Control OperationUnits with Aquazone Deluxe D Control Units with Wshp Open Multiple ProtocolPage Auxiliary Modulating Hot Water/Steam Heating Reheat Complete C and Deluxe D Board System Test LED Status Description of Operation Alarm Relay Complete C Control LED Code Fault DescriptionsLED Fault Description Code Aquazone Deluxe D Control LED IndicaService Description Status LED Test LEDESD Refrigerant Charging A50-6286ef’ to 4’ Troubleshooting Air Coil Fan Motor RemovalA50-8163 Air temperature out of range TroubleshootingCooling mode FP1125 F or Reduced or no airflow in heatReduced airflow in cooling Reduced or no water flowAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2011 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8445 A50-8446

50PCH specifications

The Carrier 50PCH is a cutting-edge series of air-cooled chillers designed to deliver exceptional cooling performance in a wide range of commercial applications. Engineered with efficiency and reliability in mind, the 50PCH stands out for its innovative technologies and robust construction, making it a preferred choice for facility managers and HVAC professionals.

One of the main features of the Carrier 50PCH is its advanced scroll compressor technology. This system consists of high-efficiency scroll compressors that optimize energy consumption while maintaining consistent cooling output. The incorporation of variable speed technology enables the chillers to adapt to fluctuating load demands, resulting in significant energy savings and reduced operational costs.

The 50PCH chillers also boast a high energy efficiency ratio (EER) and coefficient of performance (COP), ensuring compliance with stringent energy regulations and standards. They are designed with eco-friendly refrigerants, which contribute to lower greenhouse gas emissions, making them an environmentally responsible choice for modern buildings.

In addition to its energy-efficient operation, the 50PCH series is equipped with advanced controls that allow for seamless integration into building management systems. The intuitive interface facilitates monitoring and adjustment of set points, ensuring optimal comfort conditions. Furthermore, the chillers come with extensive diagnostic capabilities, enabling proactive maintenance and reducing the risk of unexpected downtime.

The robust construction of the 50PCH series enhances durability and reliability. With an all-weather aluminum cabinet, these chillers are designed to withstand harsh environmental conditions, ensuring long-term performance. The units undergo rigorous testing to meet high industry standards for quality and reliability.

Another distinguishing characteristic of the Carrier 50PCH is its whisper-quiet operation. Engineered for low sound levels, these chillers minimize noise pollution in sensitive environments, such as hospitals, schools, or residential areas.

In summary, the Carrier 50PCH series combines exceptional performance, energy efficiency, and innovative technology in a robust and reliable package. It highlights the best in modern HVAC design, making it an ideal solution for a wide array of climate control needs in commercial and institutional settings. With its advanced features and commitment to sustainability, the 50PCH is undoubtedly a leader in the air-cooled chiller market.