Carrier 50PCH specifications Coaxial Water Pressure Drop, Pressure DROP, psi kPa

Page 32

Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter- mined. See Table 26. Adjust the water control valve until the flow of 1.5 to 2 gpm is achieved. Since the pressure constantly varies, two pressure gages may be needed in some applications.

An alternative method is to install a flow control device. These devices are typically an orifice of plastic material de- signed to allow a specified flow rate that are mounted on the outlet of the water control valve. Occasionally these valves produce a velocity noise that can be reduced by applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the well water setup.

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position before flushing system.

Flushing — Once the piping is complete, units require final purging and loop charging. A flush cart pump of at least 1.5 hp is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop. Flush the loop in both directions with a high volume of water at a high velocity. Fol- low the steps below to properly flush the loop:

1.Verify power is off.

2.Fill loop with water from hose through flush cart before using flush cart pump to ensure an even fill. Do not allow the water level in the flush cart tank to drop below the pump inlet line to prevent air from filling the line.

3.Maintain a fluid level in the tank above the return tee to avoid air entering back into the fluid.

4.Shutting off the return valve that connects into the flush cart reservoir will allow 50 psig surges to help purge air pockets. This maintains the pump at 50 psig.

5.To purge, keep the pump at 50 psig until maximum pumping pressure is reached.

6.Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system.

7.A noticeable drop in fluid level will be seen in the flush cart tank. This is the only indication of air in the loop.

NOTE: If air is purged from the system while using a 10 in. PVC flush tank, the level drop will only be 1 to 2 in. since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop. If level is less than 1 to 2 in., reverse the flow.

8.Repeat this procedure until all air is purged.

9.Restore power.

Antifreeze may be added before, during or after the flushing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze section for more detail.

Loop static pressure will fluctuate with the seasons. Pres- sures will be higher in the winter months than during the warmer months. This fluctuation is normal and should be con- sidered when charging the system initially. Run the unit in either heating or cooling for several minutes to condition the loop to a homogenous temperature.

When complete, perform a final flush and pressurize the loop to a static pressure of 40 to 50 psig for winter months or 15 to 20 psig for summer months.

After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow through

the unit by checking pressure drop across the heat exchanger. Compare the results to the data in Table 26.

Table 26 — Coaxial Water Pressure Drop

50PC UNIT

 

 

 

PRESSURE DROP, psi (kPa)

 

SIZE

gpm

L/s

30 F

50 F

70 F

90 F

 

 

 

(-1 C)

(10 C)

(21 C))

(32 C)

 

0.75

0.05

0.5

(3.7)

0.3

(2.3)

0.2

(1.6)

0.2

(1.6)

006

1.1

0.07

0.8

(5.3)

0.5

(3.5)

0.4

(2.7)

0.3

(2.2)

 

1.5

0.09

1.3

(8.8)

0.9

(6.1)

0.7

(4.8)

0.6

(4.0)

 

1.1

0.07

1.3

(9.0)

0.6

(4.4)

0.4

(2.8)

0.3

(1.9)

009

1.8

0.11

2.1

(14.1)

1.4

(9.4)

1.1

(7.4)

0.9

(6.2)

 

2.3

0.14

3.5

(24.3)

2.6

(17.9)

2.1

(14.7)

1.8

(12.7)

 

1.5

0.09

1.9

(12.8)

1.1

(7.6)

0.8

(5.3)

0.6

(4.1)

012

2.3

0.15

3.6

(25.0)

2.6

(17.8)

2.1

(14.3)

1.8

(12.1)

 

3.0

0.19

6.7

(46.1)

5.0

(34.3)

4.1

(28.3)

3.6

(24.5)

 

1.9

0.12

1.0

(6.9)

0.6

(4.4)

0.5

(3.4)

0.4

(2.8)

015

2.8

0.18

1.8

(12.4)

1.4

(9.3)

1.1

(7.6)

1.0

(6.9)

 

3.8

0.24

3.3

(22.7)

2.5

(17.5)

2.1

(14.7)

1.9

(13.1)

 

2.3

0.14

2.1

(14.5)

1.4

(9.9)

1.1

(7.6)

0.9

(6.2)

018

3.4

0.21

3.4

(23.4)

2.6

(17.6)

2.1

(14.7)

1.8

(12.4)

 

4.5

0.28

5.9

(40.6)

4.6

(31.5)

3.9

(26.9)

3.4

(23.4)

 

3.0

0.19

2.2

(15.2)

1.7

(11.6)

1.4

(9.6)

1.2

(8.3)

024

4.5

0.28

4.0

(27.6)

3.2

(22.2)

2.8

(19.3)

2.5

(17.2)

 

6.0

0.38

7.2

(49.6)

5.9

(40.6)

5.2

(35.8)

4.7

(32.4)

 

3.8

0.24

1.3

(9.0)

0.9

(6.1)

0.7

(4.8)

0.6

(4.1)

030

5.6

0.35

2.3

(15.8)

1.8

(12.5)

1.5

(10.3)

1.4

(9.6)

 

7.5

0.47

4.2

(28.9)

3.4

(23.2)

2.9

(20.0)

2.6

(17.9)

 

4.5

0.28

1.8

(12.4)

1.4

(9.6)

1.2

(8.3)

1.0

(6.9)

036

6.8

0.43

3.1

(21.4)

2.4

(16.8)

2.1

(14.7)

1.9

(13.1)

 

9.0

0.57

5.4

(37.2)

4.4

(30.0)

3.8

(26.2)

3.4

(23.4)

 

5.3

0.33

2.3

(15.8)

1.8

(12.1)

1.5

(10.3)

1.3

(9.0)

042

7.9

0.50

4.3

(29.6)

3.5

(24.2)

3.1

(26.4)

2.8

(19.3)

 

10.5

0.66

7.9

(54.4)

6.5

(44.8)

5.7

(39.3)

5.2

(35.8)

 

6.0

0.38

1.8

(12.4)

1.5

(10.1)

1.3

(9.0)

1.2

(8.3)

048

9.0

0.57

3.4

(23.4)

3.0

(20.4)

2.7

(18.6)

2.6

(17.9)

 

12.0

0.76

6.2

(42.7)

5.5

(37.9)

5.1

(35.1)

4.8

(35.1)

 

7.5

0.47

3.4

(23.4)

2.8

(19.2)

2.4

(16.5)

2.2

(15.2)

060

11.3

0.71

6.8

(46.9)

5.9

(40.8)

5.4

(37.2)

5.0

(34.5)

 

15.0

0.95

12.6 (86.8)

11.1(76.8)

10.3(71.0)

9.6

(66.1)

Antifreeze — In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leaving loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F – 15 F = 15 F).

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fuming.

Calculate the total volume of fluid in the piping system. See Table 27. Use the percentage by volume in Table 28 to determine the amount of antifreeze to use. Antifreeze concen- tration should be checked from a well mixed sample using a hydrometer to measure specific gravity.

FREEZE PROTECTION SELECTION — The 30 F FP1 factory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (anti- freeze 13 F) set point to avoid nuisance faults.

Cooling Tower/Boiler Systems — These systems typ- ically use a common loop temperature maintained at 60 to 90 F. Carrier recommends using a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and

32

Image 32
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PCH,PCV Units IPT A50-8695Size A50-7842ef Electric HeatA50-8696 Side Discharge Back DischargeInstall Condensate Drain Mount the UnitA50-8489 A50-6260efA50-6261tf A50-6262efMetal Hose Minimum Bend Radii Copper FPT/PVCWire Field Power Supply FittingA50-8490 Sensor, Low Temperature Protection Air Coil A50-8491RVS Reversing Valve SolenoidA50-8492 HpwsA50-8493 LONNational Electrical Code Optional Wiring Temperature Switch A50-8440A50 86978698 Units with Deluxe D and Wshp Open Multiple Protocol ControlsWshp Open Control 50PCH,PCV Unit Electrical Data A50-8162A50-8442 Wire Field ControlsA50-8441 Rnet Wiring Specifications Rnet WiringField-Supplied Sensors for Wshp Open Controller SPT SensorsPRE-START-UP 50PCH,PCV Blower Performance Standard Unit 50PCH,PCV Blower Performance High-Static UnitFAN Rated MIN PCV Speed Airflow CFMField Selectable Inputs Complete C Control Jumper Settings Refer toDeluxe D Control Jumper Settings Refer to , 15, DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units Cooling Heating Water Flow Rate GPM50PC006 Typical Unit Operating Pressures and Temperatures 50PC009 Typical Unit Operating Pressures and Temperatures50PC012 Typical Unit Operating Pressures and Temperatures Entering Cooling Heating Water50PC015 Typical Unit Operating Pressures and Temperatures 50PC018 Typical Unit Operating Pressures and Temperatures50PC024 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat50PC030 Typical Unit Operating Pressures and Temperatures 50PC036 Typical Unit Operating Pressures and Temperatures50PC042 Typical Unit Operating Pressures and Temperatures Water Air TempUnit Start-Up Heating Mode 50PC048 Typical Unit Operating Pressures and Temperatures50PC060 Typical Unit Operating Pressures and Temperatures Unit Start-Up with Wshp Open ControlsA50-8444 BACview6 Display InterfaceGpm 30 F 50 F 70 F 90 F 10 C 21 C 32 C 006 009 Coaxial Water Pressure DropPressure DROP, psi kPa Operation Units with Aquazone Complete C ControlUnits with Aquazone Deluxe D Control Units with Wshp Open Multiple ProtocolPage Auxiliary Modulating Hot Water/Steam Heating Reheat Complete C and Deluxe D Board System Test Complete C Control LED Code Fault Descriptions LED Status Description of Operation Alarm RelayLED Fault Description Code Aquazone Deluxe D Control LED IndicaESD ServiceDescription Status LED Test LED ’ to 4’ Refrigerant ChargingA50-6286ef A50-8163 TroubleshootingAir Coil Fan Motor Removal Troubleshooting Air temperature out of rangeCooling mode FP1125 F or Reduced or no airflow in heatReduced or no water flow Reduced airflow in coolingAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm Page Copyright 2011 Carrier Corporation 50PCH,PCV START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8445 A50-8446

50PCH specifications

The Carrier 50PCH is a cutting-edge series of air-cooled chillers designed to deliver exceptional cooling performance in a wide range of commercial applications. Engineered with efficiency and reliability in mind, the 50PCH stands out for its innovative technologies and robust construction, making it a preferred choice for facility managers and HVAC professionals.

One of the main features of the Carrier 50PCH is its advanced scroll compressor technology. This system consists of high-efficiency scroll compressors that optimize energy consumption while maintaining consistent cooling output. The incorporation of variable speed technology enables the chillers to adapt to fluctuating load demands, resulting in significant energy savings and reduced operational costs.

The 50PCH chillers also boast a high energy efficiency ratio (EER) and coefficient of performance (COP), ensuring compliance with stringent energy regulations and standards. They are designed with eco-friendly refrigerants, which contribute to lower greenhouse gas emissions, making them an environmentally responsible choice for modern buildings.

In addition to its energy-efficient operation, the 50PCH series is equipped with advanced controls that allow for seamless integration into building management systems. The intuitive interface facilitates monitoring and adjustment of set points, ensuring optimal comfort conditions. Furthermore, the chillers come with extensive diagnostic capabilities, enabling proactive maintenance and reducing the risk of unexpected downtime.

The robust construction of the 50PCH series enhances durability and reliability. With an all-weather aluminum cabinet, these chillers are designed to withstand harsh environmental conditions, ensuring long-term performance. The units undergo rigorous testing to meet high industry standards for quality and reliability.

Another distinguishing characteristic of the Carrier 50PCH is its whisper-quiet operation. Engineered for low sound levels, these chillers minimize noise pollution in sensitive environments, such as hospitals, schools, or residential areas.

In summary, the Carrier 50PCH series combines exceptional performance, energy efficiency, and innovative technology in a robust and reliable package. It highlights the best in modern HVAC design, making it an ideal solution for a wide array of climate control needs in commercial and institutional settings. With its advanced features and commitment to sustainability, the 50PCH is undoubtedly a leader in the air-cooled chiller market.