Carrier 50PCH specifications Side Discharge, Back Discharge

Page 7

Supply Air

a50-6803ef

 

 

Building

 

Flexible

Loop

 

 

 

Connection

 

 

Water

 

 

Out

 

 

Water

 

 

In

Balancing Valve

 

 

(field installed

Field-supplied

and calibrated

stainless steel

accessory)

braid

hose

 

with integral

Low Pressure

“ J” swivel

Drop Water

Power

 

Control Valve

Thermostat

 

(optional)

 

(field-installed

Wiring

 

accessory)

 

Ball Valve with optional

Compressor

integral P/T plug

Access Panel

(typical for supply and

 

return piping)

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 4 — Typical Vertical Installation of 50PCV Unit

Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP:

• Units are for indoor use only.

 

 

 

• Locate in areas where ambient temperatures are between

 

40 F and 100 F and relative humidity is no greater than

 

75%.

 

 

 

Provide sufficient space for water, electrical and duct

 

connections.

 

 

 

Locate unit in an area that allows easy access and

 

removal of filter and access panels.

 

 

 

Allow enough space for service personnel to perform

 

maintenance.

 

 

 

• Return air must be able to freely enter the space if unit

 

needs to be installed in a confined area such as a closet.

• Install the unit on a piece of rubber, neoprene or other

 

mounting pad material for sound isolation. The pad

 

should be at least 3/ in. [10 mm] to

1/

2

in. [13 mm] in

 

8

 

 

 

thickness. Extend the pad beyond all four edges of the

 

unit.

 

 

 

Provide adequate clearance for filter replacement and

 

drain pan cleaning. Do not block filter access with pip-

 

ing, conduit or other materials. Refer to Fig. 1 and 3 for

 

dimensional data.

 

 

 

• Provide access for fan and fan motor maintenance and

 

for servicing the compressor and coils without removing

 

the unit.

 

 

 

• Provide an unobstructed path to the unit within the closet

 

or mechanical room. Space should be sufficient to allow

 

removal of the unit, if necessary.

 

 

 

• In limited side access installations, pre-removal of the

 

control box side mounting screws will allow control box

 

removal for future servicing.

 

 

 

• Provide access to water valves and fittings and screw-

 

driver access to the unit side panels, discharge collar and

 

all electrical connections.

 

 

 

 

NOTE: Correct placement of the horizontal unit can play an

 

important part in minimizing sound problems. Since duct-

between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 5 and 6.

NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.

Preparation — The unit should be on the ground in a well lit area for conversion. Hung units should be taken down to ground level before converting.

Water

Remove Screws

Connection End

 

Return Air

Side Discharge

Water

Connection End

Rotate

Return Air

 

Move to Side

Water

Replace Screws

Connection End

 

Return Air

Drain

Back Discharge

Discharge Air

Fig. 5 — Conversion Left Return,

Side Discharge to Back Discharge

Water

Connection End

Return Air

Supply

Duct

Side Discharge

Water

 

Connection End

Return Air

work is normally applied to these units, the unit can be

placed so that the principal sound emission is outside the oc-

cupied space in sound-critical applications. A fire damper

may be required by the local code if a fire wall is penetrated.

Drain

Discharge Air

Back Discharge

a50-6257ef

FIELD CONVERSION OF DISCHARGE AIR — The dis- charge air of the 50PCH horizontal units can be converted

Fig. 6 — Conversion Right Return, Side Discharge to Back Discharge

7

Image 7
Contents Safety Considerations ContentsGeneral InstallationPhysical Data 50PCH,PCV Units Size A50-8695IPT Electric Heat A50-7842efA50-8696 Back Discharge Side DischargeA50-6260ef Install Condensate DrainMount the Unit A50-8489Copper FPT/PVC A50-6261tfA50-6262ef Metal Hose Minimum Bend RadiiFitting Wire Field Power SupplyA50-8490 Reversing Valve Solenoid Sensor, Low Temperature Protection Air CoilA50-8491 RVSHpws A50-8492LON A50-8493A50-8440 National Electrical Code Optional Wiring Temperature Switch8697 A50Units with Deluxe D and Wshp Open Multiple Protocol Controls 8698Wshp Open Control A50-8162 50PCH,PCV Unit Electrical DataA50-8441 Wire Field ControlsA50-8442 SPT Sensors Rnet Wiring SpecificationsRnet Wiring Field-Supplied Sensors for Wshp Open ControllerPRE-START-UP PCV Speed Airflow CFM 50PCH,PCV Blower Performance Standard Unit50PCH,PCV Blower Performance High-Static Unit FAN Rated MINDeluxe D Control Jumper Settings Refer to , 15, Complete C Control Jumper Settings Refer toField Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPCooling Heating Water Flow Rate GPM Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Operating Limits 50PCH,PCV UnitsEntering Cooling Heating Water 50PC006 Typical Unit Operating Pressures and Temperatures50PC009 Typical Unit Operating Pressures and Temperatures 50PC012 Typical Unit Operating Pressures and TemperaturesTemp GPM/ton Pressure Heat 50PC015 Typical Unit Operating Pressures and Temperatures50PC018 Typical Unit Operating Pressures and Temperatures 50PC024 Typical Unit Operating Pressures and TemperaturesWater Air Temp 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and TemperaturesUnit Start-Up with Wshp Open Controls Unit Start-Up Heating Mode50PC048 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and TemperaturesBACview6 Display Interface A50-8444Pressure DROP, psi kPa Coaxial Water Pressure DropGpm 30 F 50 F 70 F 90 F 10 C 21 C 32 C 006 009 Units with Wshp Open Multiple Protocol OperationUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code Fault DescriptionsLED Status Description of Operation Alarm Relay LED Fault Description CodeDescription Status LED Test LED ServiceESD A50-6286ef Refrigerant Charging’ to 4’ Air Coil Fan Motor Removal TroubleshootingA50-8163 Reduced or no airflow in heat TroubleshootingAir temperature out of range Cooling mode FP1125 F orReduced airflow in cooling Reduced or no water flowSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Copyright 2011 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistA50-8446 Heating Cycle AnalysisCooling Cycle Analysis A50-8445

50PCH specifications

The Carrier 50PCH is a cutting-edge series of air-cooled chillers designed to deliver exceptional cooling performance in a wide range of commercial applications. Engineered with efficiency and reliability in mind, the 50PCH stands out for its innovative technologies and robust construction, making it a preferred choice for facility managers and HVAC professionals.

One of the main features of the Carrier 50PCH is its advanced scroll compressor technology. This system consists of high-efficiency scroll compressors that optimize energy consumption while maintaining consistent cooling output. The incorporation of variable speed technology enables the chillers to adapt to fluctuating load demands, resulting in significant energy savings and reduced operational costs.

The 50PCH chillers also boast a high energy efficiency ratio (EER) and coefficient of performance (COP), ensuring compliance with stringent energy regulations and standards. They are designed with eco-friendly refrigerants, which contribute to lower greenhouse gas emissions, making them an environmentally responsible choice for modern buildings.

In addition to its energy-efficient operation, the 50PCH series is equipped with advanced controls that allow for seamless integration into building management systems. The intuitive interface facilitates monitoring and adjustment of set points, ensuring optimal comfort conditions. Furthermore, the chillers come with extensive diagnostic capabilities, enabling proactive maintenance and reducing the risk of unexpected downtime.

The robust construction of the 50PCH series enhances durability and reliability. With an all-weather aluminum cabinet, these chillers are designed to withstand harsh environmental conditions, ensuring long-term performance. The units undergo rigorous testing to meet high industry standards for quality and reliability.

Another distinguishing characteristic of the Carrier 50PCH is its whisper-quiet operation. Engineered for low sound levels, these chillers minimize noise pollution in sensitive environments, such as hospitals, schools, or residential areas.

In summary, the Carrier 50PCH series combines exceptional performance, energy efficiency, and innovative technology in a robust and reliable package. It highlights the best in modern HVAC design, making it an ideal solution for a wide array of climate control needs in commercial and institutional settings. With its advanced features and commitment to sustainability, the 50PCH is undoubtedly a leader in the air-cooled chiller market.