Carrier 50PCH specifications Pre-Start-Up

Page 22

Wiring a Supply Air Temperature (SAT) Sensor — The SAT sensor is required for reheat applications.

If the cable used to wire the SAT sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.

To wire the SAT sensor to the controller:

1.Wire the sensor to the controller. See Fig. 18-20.

2.Verify that the Enable SAT jumper is on.

3.Verify that the Enable SAT and Remote jumper is in the left position.

Wiring an Indoor Air Quality (IAQ) Sensor — An IAQ sensor monitors CO2 levels. The WSHP Open controller uses this information to adjust the outside-air dampers to provide proper ventilation. An IAQ sensor can be wall-mounted or mounted in a return air duct. (Duct installation requires an aspi- rator box assembly.)

The sensor has a range of 0 to 2000 ppm and a linear 4 to

20 mA output. This is converted to 1 to 5 vdc by a 250-ohm, 1/4 watt, 2% tolerance resistor connected across the zone con- troller’s IAQ input terminals.

NOTE: Do not use a relative humidity sensor and CO2 sensor on the same zone controller if both sensors are powered off the board. If sensors are externally powered, both sensors may be used on the same zone controller.

If the cable used to wire the IAQ sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.

To wire the IAQ sensor to the controller:

1.Wire the sensor to the controller. See Fig. 18-20.

2.Install a field-supplied 250-ohm, 1/4 watt, 2% tolerance resistor across the controller’s RH/IAQ and Gnd terminals.

3.Verify the the RH/IAQ jumper is set to 0 to 5-vdc.

Wiring a Relative Humidity (RH) Sensor — The RH sensor is used for zone humidity control (dehumidification) if the WSHP unit has a dehumidification device. If not, the sensor only monitors humidity.

NOTE: Do not use a relative humidity sensor and CO2 sensor on the same zone controller if both sensors are powered off the board. If sensors are externally powered, both sensors may be used on the same zone controller.

If the cable used to wire the RH sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.

To wire the RH sensor to the controller:

1.Strip the outer jacket from the cable for at least 4 inches.

2.Strip 1/4 in. of insulation from each wire.

3.Wire the sensor to the controller.

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3 phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

9.Condensate line is open and correctly pitched.

10.Transformer switched to lower voltage tap if necessary.

11.Blower rotates freely — shipping support is removed.

12.Blower speed is on correct setting.

13.Air filter is clean and in position.

14.Service/access panels are in place.

15.Return-air temperature is between 40 to 80 F heating and 50 to 110 F cooling.

16.Air coil is clean.

17.Control field-selected settings are correct.

AIR COIL — To obtain maximum performance, clean the air coil before starting the unit. A ten percent solution of dish- washer detergent and water is recommended for both sides of the coil. Rinse thoroughly with water.

PSC (Permanent Split Capacitor) Blower Speed Selection — The PSC blower fan speed can be changed by moving the blue wire on the fan motor terminal block to the desired speed as shown in Fig. 28. The 50PC units are designed to deliver rated airflow at nominal static (0.15 in. wg) on medium speed (factory setting) and rated airflow at a higher static (0.4 to 0.5 in. wg) on high speed for applications where higher static is required. Low speed will deliver approx- imately 85% of rated airflow at 0.10 in. wg. An optional ‘high static’ blower is available by using the special option code in the model nomenclature.

NOTE: Blower performance is shown in Tables 8-10.

CONNECT THE BLUE WIRE TO:

H FOR HIGH SPEED FAN

M FOR MEDIUM SPEED FAN

L FOR LOW SPEED FAN

BLU

MEDIUM FACTORY SETTING

H

M

L

 

 

a50-6805ef

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR

Fig. 28 — Blower Speed Selection

Table 8 — 50PCV Blower Performance with

Wet Coil

COIL FACE VELOCITY

WET COIL REDUCTION

(fpm)

(in. wg)

200

0.030

250

0.055

300

0.080

350

0.100

400

0.120

450

0.140

500

0.160

22

Image 22
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data 50PCH,PCV Units Size A50-8695IPT A50-7842ef Electric HeatA50-8696 Side Discharge Back DischargeA50-8489 Install Condensate DrainMount the Unit A50-6260efMetal Hose Minimum Bend Radii A50-6261tfA50-6262ef Copper FPT/PVCWire Field Power Supply FittingA50-8490 RVS Sensor, Low Temperature Protection Air CoilA50-8491 Reversing Valve SolenoidA50-8492 HpwsA50-8493 LONNational Electrical Code Optional Wiring Temperature Switch A50-8440A50 86978698 Units with Deluxe D and Wshp Open Multiple Protocol ControlsWshp Open Control 50PCH,PCV Unit Electrical Data A50-8162A50-8441 Wire Field ControlsA50-8442 Field-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsRnet Wiring SPT SensorsPRE-START-UP FAN Rated MIN 50PCH,PCV Blower Performance Standard Unit50PCH,PCV Blower Performance High-Static Unit PCV Speed Airflow CFMDeluxe D Control Jumper Settings Refer to , 15, Complete C Control Jumper Settings Refer toField Selectable Inputs START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsOperating Limits 50PCH,PCV Units Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Cooling Heating Water Flow Rate GPM50PC012 Typical Unit Operating Pressures and Temperatures 50PC006 Typical Unit Operating Pressures and Temperatures50PC009 Typical Unit Operating Pressures and Temperatures Entering Cooling Heating Water50PC024 Typical Unit Operating Pressures and Temperatures 50PC015 Typical Unit Operating Pressures and Temperatures50PC018 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat50PC042 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures Water Air Temp50PC060 Typical Unit Operating Pressures and Temperatures Unit Start-Up Heating Mode50PC048 Typical Unit Operating Pressures and Temperatures Unit Start-Up with Wshp Open ControlsA50-8444 BACview6 Display InterfacePressure DROP, psi kPa Coaxial Water Pressure DropGpm 30 F 50 F 70 F 90 F 10 C 21 C 32 C 006 009 Units with Aquazone Deluxe D Control OperationUnits with Aquazone Complete C Control Units with Wshp Open Multiple ProtocolPage Auxiliary Modulating Hot Water/Steam Heating Reheat Complete C and Deluxe D Board System Test LED Fault Description Code Complete C Control LED Code Fault DescriptionsLED Status Description of Operation Alarm Relay Aquazone Deluxe D Control LED IndicaDescription Status LED Test LED ServiceESD A50-6286ef Refrigerant Charging’ to 4’ Air Coil Fan Motor Removal TroubleshootingA50-8163 Cooling mode FP1125 F or TroubleshootingAir temperature out of range Reduced or no airflow in heatReduced or no water flow Reduced airflow in coolingStatus Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Copyright 2011 Carrier Corporation 50PCH,PCV START-UP Checklist II. START-UPA50-8445 Heating Cycle AnalysisCooling Cycle Analysis A50-8446

50PCH specifications

The Carrier 50PCH is a cutting-edge series of air-cooled chillers designed to deliver exceptional cooling performance in a wide range of commercial applications. Engineered with efficiency and reliability in mind, the 50PCH stands out for its innovative technologies and robust construction, making it a preferred choice for facility managers and HVAC professionals.

One of the main features of the Carrier 50PCH is its advanced scroll compressor technology. This system consists of high-efficiency scroll compressors that optimize energy consumption while maintaining consistent cooling output. The incorporation of variable speed technology enables the chillers to adapt to fluctuating load demands, resulting in significant energy savings and reduced operational costs.

The 50PCH chillers also boast a high energy efficiency ratio (EER) and coefficient of performance (COP), ensuring compliance with stringent energy regulations and standards. They are designed with eco-friendly refrigerants, which contribute to lower greenhouse gas emissions, making them an environmentally responsible choice for modern buildings.

In addition to its energy-efficient operation, the 50PCH series is equipped with advanced controls that allow for seamless integration into building management systems. The intuitive interface facilitates monitoring and adjustment of set points, ensuring optimal comfort conditions. Furthermore, the chillers come with extensive diagnostic capabilities, enabling proactive maintenance and reducing the risk of unexpected downtime.

The robust construction of the 50PCH series enhances durability and reliability. With an all-weather aluminum cabinet, these chillers are designed to withstand harsh environmental conditions, ensuring long-term performance. The units undergo rigorous testing to meet high industry standards for quality and reliability.

Another distinguishing characteristic of the Carrier 50PCH is its whisper-quiet operation. Engineered for low sound levels, these chillers minimize noise pollution in sensitive environments, such as hospitals, schools, or residential areas.

In summary, the Carrier 50PCH series combines exceptional performance, energy efficiency, and innovative technology in a robust and reliable package. It highlights the best in modern HVAC design, making it an ideal solution for a wide array of climate control needs in commercial and institutional settings. With its advanced features and commitment to sustainability, the 50PCH is undoubtedly a leader in the air-cooled chiller market.