50CR
Check system wiring to be sure the User Interface is powered and connections are made A to A, B to B, etc., and wiring is not shorted.
Shorting or
STATUS CODE 46, BROWNOUT CONDITION
If the secondary voltage of the transformer falls below
When secondary voltage rises above
STATUS CODE 53, OUTDOOR AIR TEMPERATURE SENSOR FAULT
If an OAT sensor is found at
Check for faults in wiring connecting sensor to OAT terminals. Using an Ohm meter, check resistance of thermistor for a short or open condition.
If thermistor is shorted or open, replace it to return the system to normal operation. If fault is in the wiring connections, correcting the fault will clear the code and return the system to normal operation.
NOTE: If fault condition is an open thermistor or a wiring problem that appears to be an open thermistor and the power to the unit is cycled off, the fault code will be cleared on the next
This is because on
Step 2—Sequence of Operation
The packaged heat pump is designed for installation with a communicating User Interface. This unit will not respond to commands provided by a common thermostat except under certain emergency situations described in Step
The User Interface uses temperature, humidity and other data supplied from indoor and outdoor system components to control heating or cooling system for optimum comfort. The unit will be commanded by User Interface to supply airflow. The unit will operate the indoor blower at requested airflow for most modes.
The nominal requested airflow will be 350 cfm per ton of nominal cooling capacity as defined by unit size. Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfort and system efficiency. Refer to User Interface literature for further system control details.
Airflow during electric heater operation must be greater than a minimum level for safe operation. If User Interface instructs unit to turn on electric heat and the requested airflow is less than the minimum level the unit control will override requested value.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 4 minutes have elapsed. The cooling cycle remains “on” until the room temperature drops to point that is slightly below the cooling control setting of the user interface. Additionally, there is a
Step 3—Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
1.Use both high- and
2.Repair leak following accepted practices.
NOTE: Install a
3.Check system for leaks using an approved method.
4.Evacuate refrigerant system and reclaim refrigerant if no additional leaks are found.
5.Charge unit with Puron
Step 4—Start-Up Adjustments
Complete the required procedures given in the
CHECKING COOLING AND HEATING CONTROL OPERATION
Start and check the unit for proper control operation as follows:
1.Place room UI SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down within 60 sec
2.Place system switch or MODE control in HEAT position. Set control above room temperature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down when control setting is satisfied.
3.When using an automatic changeover room thermostat, place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in cooling mode when temperature control is set to “call for cooling” (below room temperature), and unit operates in heating mode when temperature control is set to “call for heating” (above room temperature).
IMPORTANT:
20