Table 7—Troubleshooting Chart
SYMPTOM | CAUSE | REMEDY | |
|
|
| |
| Power failure | Call power company | |
| Fuse blown or circuit breaker tripped | Replace fuse or reset circuit breaker | |
| Defective contactor, transformer, control relay, defrost | Replace component | |
| board, or | ||
|
| ||
|
|
| |
Compressor and outdoor fan | Insufficient line voltage | Determine cause and correct | |
|
| ||
will not start | Incorrect or faulty wiring | Check wiring diagram and rewire correctly | |
| |||
|
|
| |
| User Interface setting too low/too high | Reset UI setting | |
|
|
| |
|
| DO NOT bypass this compressor time | |
| Units have a | ||
|
| relay is | |
|
|
| |
| Faulty wiring or circuit | Check wiring and repair or replace | |
| Loose connections in compressor | ||
|
| ||
|
|
| |
| Compressor motor burned out, seized, or | Determine cause | |
Compressor will not start but condenser fan | internal overload open | Replace compressor | |
|
| ||
Defective run capacitor, overload, or PTC (positive |
| ||
runs | Determine cause and replace | ||
temperature coefficient) thermistor | |||
|
| ||
|
|
| |
| One leg of | Replace fuse or reset circuit breaker | |
| Determine cause | ||
|
| ||
|
|
| |
| Low input voltage (20 percent low) | Determine cause and correct | |
| Scroll compressor is rotating in the wrong direction | Correct the direction of rotation by reversing the | |
060 unit) has a low pressure differential | |||
| |||
|
|
| |
| Refrigerant overcharge or undercharge | Recover refrigerant, evacuate system, and re- | |
| charge to capacities shown on rating plate | ||
|
| ||
|
|
| |
| Defective compressor | Replace and determine cause | |
Compressor cycles (other than normally satis- | Insufficient line voltage | Determine cause and correct | |
Blocked outdoor coil | Determine cause and correct | ||
fying) cooling/heating calls | |||
Defective run/start capacitor, overload or start relay | Determine cause and replace | ||
| |||
| Faulty outdoor fan motor or capacitor | Replace | |
| Damaged reversing valve | Determine cause and correct | |
| Restriction in refrigerant system | Locate restriction and remove | |
| Dirty air filter | Replace filter | |
| Unit undersized for load | Decrease load or increase unit size | |
| UI temperature set too low/too high | Reset UI setting | |
| Low refrigerant charge | Locate leak, repair, and recharge | |
Compressor operates continuously |
| Check defrost time settings | |
Frosted coil with incorrect defrost operation | Reset as necessary | ||
| Check defrost temperature switch | ||
|
| ||
|
| Replace as necessary | |
|
|
| |
| Air in system | Recover refrigerant, evacuate system, and re- | |
| charge | ||
|
| ||
|
|
| |
| Outdoor coil dirty or restricted | Clean coil or remove restriction | |
| Dirty air filter | Replace filter | |
| Dirty indoor or outdoor coil | Clean coil | |
| Refrigerant overcharged | Recover excess refrigerant | |
Excessive head pressure |
|
| |
Air in system | Recover refrigerant, evacuate system, and re- | ||
| charge | ||
|
| ||
|
|
| |
| (Heat) Indoor air restricted or recirculating | Determine cause and correct | |
| Indoor or outdoor air restricted or air | Determine cause and correct |