Carrier 50CR installation instructions Troubleshooting Chart Cont’d, Head pressure too low

Page 31

Table 7—Troubleshooting Chart (Cont’d)

SYMPTOM

CAUSE

REMEDY

 

 

 

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

 

 

(Cool) High Heat load

Check for source and eliminate

Excessive suction pressure

Reversing valve hung up or leaking internally

Replace valve

 

Refrigerant overcharged

Recover excess refrigerant

 

(Cool) Dirty air filter

Replace filter

 

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes between

 

defrost cycles

 

 

 

 

 

 

Low refrigerant charge

Check for leaks, repair and recharge

Suction pressure too low

Metering device or low side restricted

Remove source of restriction

(Cool) Insufficient coil airflow

Increase air quantity

 

 

Check filter–replace if necessary

 

 

 

 

 

 

(Cool) Temperature too low in conditioned area

Reset UI setting

 

(Cool) Outdoor ambient below 55°F

Install low--ambient kit

 

Filter drier restricted

Replace

Compressor runs but outdoor fan does not

NC (normally closed) contacts on defrost board

Check condition of relay on board

open

Replace if necessary

 

 

 

 

 

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

IFM does not run

Insufficient voltage at motor

Determine cause and correct

 

Power connectors not properly sealed

Connectors should snap easily; do not force

 

Water dripping into motor

Verify proper drip loops in connector wires

IFM operation is intermittent

Connectors not firmly sealed

Gently pull wires individually to be sure they are

 

crimped into the housing

 

 

IFM-Indoor Fan Motor

50CR

31

Image 31
Contents Table of Contents Installation InstructionsIntroduction Safety ConsiderationsElectrical Shock Hazard Equipment Damage HazardRoof Curb for Small Cabinet Roof Curb for Large Cabinet Unit Leveling Tolerances 50CR024-036 Unit Dimensions 50CR042-060 Unit Dimensions Property Damage Hazard Rig and Place UnitInspection Unit Falling HazardRigging Bracket Under Unit Rain Lip Electrical Operation Hazard Select and Install DuctworkProvide for Condensate Disposal Physical Data Unit 50CR Typical InstallationHIGH-VOLTAGE Connections Routing Power Leads Into UnitConnecting Ground Lead to Ground Screw Routing Control Power WiresElectrical Data-50CR Electrical Data Legend Wiring Schematics-50CR Single Phase Wiring Schematics-50CR Three Phase Line Power Connections Accessory InstallationSTART-UP PRE-START-UP FIRE, EXPLOSION, Electrical Shock HazardUnit Start-Up Verify Motor Winding Section Status Code 45, Control Board Test FaultStatus Code 37, Heater Output Sensed on When not Energized Status Code 44, Motor Communication FaultStatus Code 25, Invalid Motor / Model Selection Status Code 36, Heater Output not Sensed When EnergizedStatus Code 41, Blower Motor Fault Status Code 16, System Communication FaultSequence of Operation Start-Up AdjustmentsCheck for Refrigerant Leaks Typical Heat Pump Operation, Cooling Mode Defrost Control Electric Heat Pressure Drop Table Small Cabinet Personal Injury and Unit Damage Hazard MaintenanceUnit Operation Hazard Outdoor Fan Air FilterIndoor Blower and Motor Outdoor Coil, Indoor Coil, and Condensate Drain PanIndoor Airflow Pressure SwitchesMetering Devices-TXV & Accurater Piston EXPLOSION, FIRE, Electrical Shock Hazard High-Pressure SwitchPersonal INJURY, Unit Operation Hazard System Information LOSS-OF-CHARGE SwitchTroubleshooting START-UP ChecklistObserve all warnings, cautions, and bold text Troubleshooting Chart Head pressure too low Troubleshooting Chart Cont’dSTART-UP Checklist