Carrier 50CR Indoor Airflow, Metering Devices-TXV & Accurater Piston, Pressure Switches

Page 26

Balance Point Worksheet

50CR

 

 

 

70

Based on Entering Indoor Air of 70 Deg. F and Rated CFM

 

 

 

 

 

 

Building Heat Loss, 1000BTUH

Unit Integrated Heating Capacity,

 

60

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

1000BTUH

40

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

Outdoor Air Temp (Deg F)

060

048

042

036

030

024

C03008

Fig. 25 - 50CR Balance Point Worksheet

Step 6—Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.

If oil is detected or if low performance is suspected, leak test all refrigerant tubing using an electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.

Step 7—Indoor Airflow

The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean.

Step 8—Metering Devices-TXV & Accurater Piston

This unit uses 2 types of metering devices. The outdoor metering device is a fixed orifice and is contained in the brass-hex body in the liquid line feeding the outdoor coils. The indoor metering device is a TXV-type device.

Step 9—Pressure Switches

Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R-410A) systems. R-22 pressure switches must not be used as replacements for the Puron (R-410A) system.

C99097

Fig. 26 - Refrigerant Circuit

Step 10—Loss-of-Charge Switch

This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low

26

Image 26
Contents Installation Instructions Table of ContentsEquipment Damage Hazard Safety ConsiderationsElectrical Shock Hazard IntroductionRoof Curb for Small Cabinet Roof Curb for Large Cabinet Unit Leveling Tolerances 50CR024-036 Unit Dimensions 50CR042-060 Unit Dimensions Unit Falling Hazard Rig and Place UnitInspection Property Damage HazardRigging Bracket Under Unit Rain Lip Provide for Condensate Disposal Select and Install DuctworkElectrical Operation Hazard Typical Installation Physical Data Unit 50CRRouting Control Power Wires Routing Power Leads Into UnitConnecting Ground Lead to Ground Screw HIGH-VOLTAGE ConnectionsElectrical Data-50CR Electrical Data Legend Wiring Schematics-50CR Single Phase Wiring Schematics-50CR Three Phase Accessory Installation Line Power ConnectionsUnit Start-Up PRE-START-UP FIRE, EXPLOSION, Electrical Shock HazardSTART-UP Status Code 44, Motor Communication Fault Status Code 45, Control Board Test FaultStatus Code 37, Heater Output Sensed on When not Energized Verify Motor Winding SectionStatus Code 16, System Communication Fault Status Code 36, Heater Output not Sensed When EnergizedStatus Code 41, Blower Motor Fault Status Code 25, Invalid Motor / Model SelectionCheck for Refrigerant Leaks Start-Up AdjustmentsSequence of Operation Typical Heat Pump Operation, Cooling Mode Defrost Control Electric Heat Pressure Drop Table Small Cabinet Unit Operation Hazard MaintenancePersonal Injury and Unit Damage Hazard Outdoor Coil, Indoor Coil, and Condensate Drain Pan Air FilterIndoor Blower and Motor Outdoor FanMetering Devices-TXV & Accurater Piston Pressure SwitchesIndoor Airflow Personal INJURY, Unit Operation Hazard High-Pressure SwitchEXPLOSION, FIRE, Electrical Shock Hazard START-UP Checklist LOSS-OF-CHARGE SwitchTroubleshooting System InformationObserve all warnings, cautions, and bold text Troubleshooting Chart Troubleshooting Chart Cont’d Head pressure too lowSTART-UP Checklist